9 Test run
  Before test run
 y Before turning on the power supply, carry out the 
following procedure.
1) By using insulation tester (500VMΩ), check that 
resistance of 1MΩ or more exists between the 
terminal block L to N and the earth (grounding).  
If resistance of less than 1MΩ is detected, do not 
run the unit.
2) Check the valve of the outdoor unit being opened 
fully.
 y To protect the compressor at activation time, leave 
power-ON for 12 hours or more be for operating.
 y Before starting a test run, be sure to set addresses 
following the installation manual supplied with the 
outdoor unit.
 ◆ Requirements for turning 
thermostat OFF
Cooling operation
 y When the outdoor/suction air temperature is lower 
than or equal to 19 °C.
 y When the outdoor/suction air temperature is lower 
than or equal to 3 °C above the set temperature.
Cooling operation
 y When the outdoor/suction air temperature is lower 
than or equal to -10 °C
 y When the outdoor/suction air temperature is higher 
than or equal to 15 °C.
 y When the outdoor/suction air temperature is higher 
than or equal to 3 °C above the set temperature.
  Execute a test run
 y When a fan operation is to be performed for  
an individual indoor unit, turn off the power, short 
circuit CN72 on the circuit board, and then turn the 
power back on. (Set the operation mode to “fan” 
to operate the unit.) When the test run has been 
performed using this method, be sure to release the 
short circuit of CN72 after the test run is completed.
Operate the unit with the remote controller as usual.
For the procedure of the operation, refer to the 
Owner’s Manual attached to the outdoor unit. A forced 
test run can be executed in the following procedure 
even if the operation stops by thermostat-OFF.
In order to prevent a serial operation, the forced test 
run is released after 60 minutes have passed and 
returns to the usual operation.
Wired remote controller
Be sure to stop the air conditioner before making 
settings.
(Change the setup while the air conditioner is not 
working.)
1 23
3
4
1
Push and hold OFF timer button and [ ]  
setting button simultaneously for 10 
seconds or more. [TEST] is displayed 
on the display part and the test run is 
permitted.
2
Push ON/OFF button.
3
Push menu button to select the operation 
mode. Select [   Cool] with [ ] [ ] setting 
button, and then push menu button  
(three times) again to determine the 
operation mode.
 y Do not run the air conditioner in a mode other 
than [Cool].
 y The temperature setting function does notwork 
during test run.
 y The check code is displayed as usual.
 
CAUTION
Do not use the forced test run for cases other than 
the test run because it applies an excessive load to 
the devices.
4
After the test run, push OFF timer button to 
stop a test run.
([TEST] disappears on the display and the air 
conditioner enters the normal stop mode.)
Wireless remote controller
1
Turn on the power of the air conditioner. 
When power is turned on for the rst time 
after installation, it takes approx. 5 minutes 
until the remote controller becomes 
available. In the case of subsequent  
power-on, it takes approx. 1 minute until 
the remote controller becomes available.
Execute a test run after the predetermined 
time has passed.
2
Push “ON/OFF” button on the remote 
controller, select [   Cool] with “MODE” 
button, and then select [  HIGH] 
with “FAN” button.
3
Set the temperature to 17°C with the temp. 
setup buttons.
4
After conrming a signal receiving sound 
“beep” immediately set the temperature to 
18°C with the temp. setup buttons.
5
After conrming a signal receiving sound 
“beep” immediately set the temperature to 
17°C with the temp. setup buttons.
6
Repeat procedures 4 → 5 → 4 → 5.
Indicators “Operation” (green), “Timer” 
(green), and “Ready” (orange) in the 
wireless receiver section ash in approx. 
10 seconds, and the air conditioner starts 
operation. If any of these indicators does 
not fash, repeat procedures 2 to 5.
7
Upon completion of the test run, push
“ON/OFF” button to stop operation.
<Overview of test run operations using the wireless 
remote controller>
 q Cooling test run:
ON/OFF → 17°C → 18°C → 17°C → 18°C → 17°C→ 
18°C → 17°C → (test run) → ON/OFF