8 Applicable controls
REQUIREMENT
When the air conditioner is used for the rst time, it
will take some moments after the power has been
turned on before the remote controller becomes
available for operations: This is normal and is not
indicative of trouble.
y Concerning the automatic addresses
(The automatic addresses are set up by
performing operations on the outdoor interface
circuit board.)
While the automatic addresses are being set up,
no remote controller operations can be performed.
Setup takes up to 10 minutes (usually about
5 minutes).
y When the power is turned on after automatic
address setup
It takes up to 10 minutes (usually about 3 minutes)
for the outdoor unit to start operating after the
power has been turned on.
Before the air conditioner was shipped from the
factory, all units are set to [STANDARD]
(factory default).
If necessary, change the indoor unit settings.
The settings are changed by operating the wired
remote controller.
* The settings cannot be changed using only
a wireless remote controller, simple remote
controller or group control remote controller
by itself so install a wired remote controller
separately as well.
Applicable controls setup
(settings at the site)
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
Set only the CODE No. shown in the following table:
DO NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible
to operate the air conditioner or other trouble with
the product may result.
3,6 2,4,5
4,5 1 7
1
Push and hold menu button and [ ] setting
button simultaneously for 10 seconds or
more.
y After a while, the display ashes as shown in the
gure. “ALL” is displayed as indoor unit numbers
during initial communication immediately after
the power has been turned on.
Indoor unit No.
Installing indoor unit on high
ceiling
When an indoor unit is installed on a ceiling higher
than the standard height, make the high-ceiling setting
for fan speed adjustment.
Follow to the basic operation procedure
(123456).
y For the CODE No. in Procedure 4, specify [5d].
y Select the SET DATA for Procedure 5 from the
“Height list of ceiling possible to be installed” table in
this manual.
Remote controller-less setting
Change the high-ceiling setting with the DIP switch on
the receiver section P.C. Board.
For details, refer to the manual of the wireless remote
controller kit. The settings can also be changed with
the switch on the indoor microcomputer P.C. Board.
* Once the setting is changed, setting to 0001 or 0003
is possible, however setting to 0000 requires a
setting data change to 0000 using the wired remote
controller (separately sold) with the normal switch
setting (factory default).
MCU(IC501)
SW501-2
SW501-1
SET DATA SW501-1 SW501-2
0000
(Factory default)
OFF OFF
0001 ON OFF
0003 OFF ON
To restore the factory defaults
To return the DIP switch settings to the factory
defaults, set SW501-1 and SW501-2 to OFF, connect
a separately sold wired remote controller, and then set
the data of CODE No. [5d] to “0000”.
2
Each time [ ] [ ] setting button is pushed,
indoor unit numbers in the group control
change cyclically. Select the indoor unit to
change settings for.
y The fan of the selected indoor unit runs.
The indoor unit can be conrmed for which to
change settings.
3
Push OFF timer button to conrm the
selected indoor unit.
Set data
Code No.
4
Push the menu button to make Code No.
[ ] ash. Change Code No. [ ] with
[ ] [ ] setting button.
5
Push the menu button to make Set data
[ ] ash. Change Set [ ] with
[ ] [ ] setting button.
6
Push OFF timer button.
By doing so, the setup is completed.
y To change other settings of the selected indoor
unit, repeat from Procedure 4.
7
When all the settings have been completed,
push ON/OFF button to determine the
settings.
” ashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while “ ” is ashing.)
y To change settings of another indoor unit,
repeat from Procedure 1.