Fig. 6 — 42SGS Furred-In Slave Stack Dimensions
*Drawing provided for reference only. Dimensions may vary with options ordered.
NOTES:
1. Units are fabricated of 18-gage galvanized steel with a 16-gage galvanized fan deck.
2. All risers are insulated with closed cell insulation.
3. Thermostats shipped loose for field connection.
4. Risers are piped to coil with valves as specified.
5. Blower, motor, valves, coil, and filter are accessible through the return air opening.
6. Unit and control box are insulated.
7. Riser length = [(floor to floor) +2-in.], maximum riser length = 119-in.
8. Maximum riser size is 2
1
/
2
-in. diameter. If larger sizes are required, please consult the factory.
9. Expansion loops in hot water heating circuits as required.
10. A 9-in. x 2
1
/
4
-in. slot is provided in the inside back panel for coil connection penetration to permit expansion and con-
traction of risers. Care must be taken to position the risers so that coil connection is at center of slot.
11. Drawing is pictorial (see unit arrangements for actual supply and return air orientation).
12. All dimensions are in inches.
†Unit weights are based on dry coils and minimum rows. Weights exclude packaging, valves, and other components.
UNIT
SIZE
NOM
AIRFLOW
(CFM)
DIMENSIONS (in.)
UNIT
WEIGHT†
(lb)
SINGLE
SUPPLY
DOUBLE
SUPPLY
TOP SUPPLY
EGH I
ABABCD
03 300 14 8 14 6 14 10 17 1
1
/
2
1
1
/
2
14 162
04 400 14 12 14 6 14 10 17 1
1
/
2
1
1
/
2
14 203
06 600 18 10 18 6 16 12 20 1 2 18 216
08 800 18 12 18 6 16 12 20 1 2 18 234
10 1000 — — 22 8 18 16 24 1 3 22 252
12 1200 — — 22 8 18 16 24 1 3 22 275
**Factory-Installed.
††Field-Installed.
ITEM DESCRIPTION QTY
1 Electrical Knockouts
1
2 Strip Heater** (Optional) 1
3 Limit Switch**†† (Optional) 1
4
1
/
2
-in. Isolation Ball Valves** 2/4
5 Coil Stub Outs 2/4
6 Shipping Brace 2/4
7 Flexible Drain Tube/P-Trap 1
8 Coil
1
/
2
-in. OD Copper Tube
1
9 Filter, Throwaway, 1-in.** 1
10 Return Air Opening 1
11 Air Vent, Manual 1
12 Knockout (For Optional Remote Mounting) 2
13 Molex Connector for Field-Installed Stat 1
14 Control Box 1
15 Drain Pan 1
16 Return Air Blockoff Panel (Optional) 1
17 Blower 1
18 Motor, 3-Speed, PSC, with Quick Connect 1
19 Access Panel (Control Box) 1
20
Control Opening (Surface Mount
Thermostat)
1
21 Duct Collar,
1
/
2
-in. Extension (Typical)
1/2/3
22 Supply Air Opening(s) 1/2/3
23
Top Supply Duct Collar 1-in. Extension
(Optional)
1
23
LEGEND
CR — Cold Water Return
CS — Cold Water Supply
D—Drain
HR — Hot Water Return
HS — Hot Water Supply
R—Return
S—Supply