45MBDAQ: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
26
CONDENSATE DRAIN AND CONDENSATE
LIFT PUMP INSTALLATION (HORIZONTAL
INSTALLATION)
For sizes 9, 12 and 18, the condensate lift pump is provided in a separate box.
Use the following steps to install the External Condensate Lift Pump for a
horizontal installation of the indoor unit.
NOTE: Drain connections A, B and C are covered with caps.
1. For sizes 09K and 12K:
a. Remove the cap on the drainage outlet.
b. Cut both ends of the rubber tubing provided into a straight one.
c. Connect the drainage outlet and condensate lift pump using the
rubber tubing and secure it with clamps on both ends (see Fig. 41).
d. Plug the power cable of the external pump to CN13 / “PUMP”
pin and plug the water level sensor cable to the CN5 /
“WATER” to enable the pump (see Fig. 45).
2. For size 18K:
a. R
emove the cap on drain connector B.
b. Connect drain connector B and the condensate lift pump using
the L rubber hose and secure it with clamps on both ends.
c. Connect the drainpipe to connector D (see Fig. 42).
d. Plug the power cable of the external pump to CN13 / “PUMP”
pin and plug the water level sensor cable to CN5 / “WATER”
to enable the pump (see Fig. 43).
Fig. 41 —Condensate lift pump installation sizes 09K12K
Fig. 42 —Condensate lift pump installation size 18K
3.
Sizes 24K, 36K, 48K and 58K have a built-in condensate lift pump
. Drain
connections (A, B and C) are covered with caps.
Connect the drainpipe to connector D (see Fig. 43).
Fig. 43 —Connection of drain pipe to condensate lift pump sizes 24-58K
Disabling the Condensate Lift Pump
The pump must be disabled while the unit is installed vertically (upflow)
or the lift pump assembly is removed from its original position:
Open the Control Box assembly cover, unplug the “CN13 PUMP” pin
to disable the pump function, and short-connect the “CN5 WATER”
plug to disable the water level sensor by either splicing the wires
coming out of the CN5 WATER plug or by using a jumper plug
Replacement Component part number 17401204000333 (optional in
some units otherwise sold separately) (see Figures 44 and 45).
Fig. 44 —Disable condensate lift pump
Fig. 45 —Condensate Lift Pump Connectors
Connector A
Connector B
Connector C
Connector D
Hose
Connector A
Connector B
Connector C
Connector D
Remove
the cover
Short connect the “CN5water
Unplug the CN13 “PUMP” plug pin
PIN CN13
“PUMP”
PIN CN5
“WATER”