45MBDAQ: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
33
USING THE 120L WIRED CONTROLLER
To set Static Pressure Airflow
The factory default setting is SP1, The external static pressure can be
manually changed to the fan curves 1,2,3,4,5,6,7,8.
a. Press and hold ON/OFF and FAN for approximately 7 sec-
onds.
b. Press “∧” or “∨” to scroll through the menu and select 8.
c. Press and hold ON/OFF for approximately 2 seconds, Press “
∧” or “∨” to scroll through and select 1-8.
d. Press the check mark or OK and the display board displays
CS.
e. Press and hold ON/OFF and FAN for approximately 7
seconds, Then exit test mode.
To set Static Pressure Airflow
Use the Automatic Airflow “AF” Adjustment function to realize
Real-time constant airflows.
a. Press and hold ON/OFF and FAN for approximately 7
seconds.
b. Press “∧” or “∨” to scroll through the menu and select “8”.
c. Press and hold ON/OFF for approximately 2 seconds. Press “
∧” or “∨” to scroll through and select “AF”.
d. Press check mark or “OK” and the display board displays
“CS”.
e. Press and hold ON/OFF and FAN for approximately 7
seconds, Then exit test mode.
NOTE: Before commissioning, check the power connection of the
machine, turn on the power, and keep the machine not
working.
NOTE: If there is no change after airflow adjustment, perform the
setting again.
NOTE: Low static pressure series 06K,09K,12K,18K models, SP
options can only be 1-4.
WHEN USING THE 120N WIRED
CONTROLLER
To Set Static Pressure Air Flow
The factory default setting is SP1, The external static pressure can be
manually changed to the fan curves 1,2,3,4,5,6,7,8.
a. Press and hold Copy for approximately 3 seconds. The lower
right corner displays P:00, Press OK.
b. Press “∧” to scroll through the menu. The lower right corner
shows SP, Press ?OK.
c. Press “∧” or “∨” to scroll through the menu and select 1-8,
Press OK.
d. Press “Back” to exit the test mode.
To Set Real-Time Constant Air Flow
Use the Automatic Airflow “AF” Adjustment function to realize
Real-time constant airflows.
a. Press and hold Copy for approximately 3 seconds. The lower
right corner shows P:00, Press “OK”.
b. Press “∧” to scroll through the menu. The lower right corner
shows AF. Press “OK”.
c. Press “Back” to exit the test mode.
NOTE: T1, T2, T2b, T3, T4 are sub-menus for thermistors. DO
NOT select to set the external static pressure.
NOTE: Before commissioning, check the power connection of the
machine, turn on the power, and keep the machine not
working.
NOTE: If there is no change after airflow adjustment, perform the
setting again.
NOTE: Setting Static Pressure or Automatic Airflow need to use the
Wired Remote Controller.
NOTE: Low static pressure series 06K,09K,12K,18K models, SP
options can only be “ 1~4 ”.