APPENDIX A LOCAL DISPLAY AND CCN TABLES (CONT)
MODE SET POINTS
ITEM EXPA NSION RANGE UNITS DEFA ULT
CCN TABLE/
S U B --- T A B L E
CCN POINT
SETPOINT CONFIGURATION
SETPOINTS SET_PNT
OCSP Occupied Cool Setpoint 55 t o 80F dF 78 OCSP
UCSP Unoccupied Cool Setpoint 75 to 95F dF 85 UCSP
OHSP Occupied Heat Setpoint 55 to 80F dF 68 OHSP
UHSP Unoccupied Heat Setpoint 40 to 80F dF 60 UHSP
GAP Heat--- Cool Setpoint Gap 2 to 10F dF 5 HCSP_GAP
STO.R SPT Offset Range (+/--- ) 0to5F ^F 5 SPTO_RNG
RH.SP Space RH Setpoint 30 t o 95 % 50 SPRH_SP
RH.DB Space RH Deadband 2to20 % 5 SPRH_DB
RH.HB Reheat Heat SP Deadband --- 5 t o 5 ^F 2 RH_HSPDB
CA.LO CircuitALockoutTemp 0 to 100F dF 0 OATLCMPA
CB.LO CircuitBLockoutTemp 0 to 100F dF 0 : n o H u m i d i --- M i Z e r F I O P
H u m i d i --- M i Z e r F I O P :
40 (03--- 16)
0 (20--- 28)
OATLCMPB
CC.LO CircuitCLockoutTemp 0 t o 100F dF 0 OATLCMPC
HT.LO Heating Lockout Temp 40 to 125F dF 75 OATLHEAT
EH.LO Econo Cool H i Temp Limit 40 to 100F dF 65 OATLECLH
EL.LO Econo Cool Lo Temp Limit
--- 3 0 t o
50F
dF 0 OATLECLL
FC.LO Free Cool Low Temp Limit 0 to 70F dF 50 OATLUEFC
LCSP Low Cool SAT Setpoint 55 to 75F dF
55 (03--- 07)
65 (08--- 28)
LCSASP
HCSP High Cool SAT Setpoint 50 t o 70F dF 55 HCSASP
MODE INPUTS
ITEM EXPA NSION RANGE UNITS
CCN TABLE/
S U B --- T A B L E
CCN POINT
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
STATUS DISPLAY
INPUTS UINPUT
STAT Thermostat Inputs
Y1 Thermostat Y1 Input On/Off Y1 forcible
Y2 Thermostat Y2 Input On/Off Y2 forcible
W1 Thermostat W1 Input On/Off W1 forcible
W2 Thermostat W2 Input On/Off W2 forcible
G Thermostat G Input On/Off G forcible
GEN.I General Inputs
FIL.S Filter Status Switch Dirty/Clean FILTSTAT forcible
FAN.S Fan Status Switch On/Off FAN_STAT forcible
FDWN Fire Shutdown Switch On/Off FIREDOWN forcible
ENTH Outdoor Enthalpy Switch High/Low ENTHALPY forcible
RM.OC Remote Occupancy Switch On/Off REM_OCC forcible
HUM Space Humidity Switch High/Low HUM_STAT forcible
CS.IN Current Sensor Inputs
CS.A1 Compressor A1 Feedback On/Off CS_A1
CS.A2 Compressor A2 Feedback On/Off CS_A2
CS.B1 Compressor B1 Feedback On/Off CS_B1
CS.C1 Compressor C1 Feedback On/Off CS_C1
AIR.Q Air Quality Inputs
IAQ.S IAQ Level (switch) High/Low IAQIN forcible forcible
IAQ IAQ Level (sensor) xxxx ppm IAQ forcible forcible
OAQ OAQ Level (sensor) xxxx ppm OAQ forcible forcible
SP.RH Space Humidity Sensor xxx.x % SPRH forcible forcible