APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — RUN STATUS (cont)
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S U B --- T A B L E
CCN POINT
CCN WRITE
STATUS
HEAT Heating Status HEATDISP
DMD.H Heating Demand xxx.x ^F HEAT_DMD
AVL.H Available Heating Stages x AVLHSTGS
REQ.H Requested Heating Stages x REQHSTGS
MAX.H Max Allowed Heat Stages x MAXHSTGS forcible
LMT.H Max Heat Stage In Effect x HSTGLIMT
IDF Indoor Fan State On/Off IDFSTATE
F.SPD Commanded Fan Speed xxx FANSPEED
HT.1 Heat Stage 1 Relay On/Off HEAT_1
TG.H1 Heat Stage 1 Timeguard xxx sec TIMGD_H1
HT.2 Heat Stage 2 Relay On/Off HEAT_2
TG.H2 Heat Stage 2 Timeguard xxx sec TIMGD_H2
ECON Economizer Status ECONDISP
EC.CP Econo Commanded Position xxx % ECONOCMD
EC.AP Econo Actual Position xxx % ECONOPOS
EC.MP MinPositioninEffect xxx % MIN_POS forcible
IAQ.S IAQ Level (switch) High/Low IAQIN
IAQ IAQ Level (sensor) xxxx ppm IAQ
OAT Outdoor Air Temperature xxx.x dF OA_TEMP
ENTH Outdoor Enthalpy Switch High/Low ENTHALPY
OAQ OAQ Level (sensor) xxxx ppm OAQ
PE.1 Power Exhaust 1 Relay On/Off PE_1
PE.2 Power Exhaust 2 Relay On/Off PE_2
HRS Component Run Hours STRTHOUR
A1 Compressor A1 Run Hours xxxxx.xx hours HR_A1 forcible
A2 Compressor A2 Run Hours xxxxx.xx hours HR_A2 forcible
B1 Compressor B1 Run Hours xxxxx.xx hours HR_B1 forcible
C1 Compressor C1 Run Hours xxxxx.xx hours HR_C1 forcible
CCH Crankcase Heat Run Hours xxxxx.xx hours HR_CCH forcible
IDF Indoor Fan Run Hours xxxxx.xx hours HR_IDF forcible
OFC.1 Outdoor Fan 1 Run Hours xxxxx.xx hours HR_OFC_1 forcible
OFC.2 Outdoor Fan 2 Run Hours xxxxx.xx hours HR_OFC_2 forcible
OFC.3 Outdoor Fan 3 Run Hours xxxxx.xx hours HR_OFC_3 forcible
HT.1 Heat Stage 1 Run Hours xxxxx.xx hours HR_HTR_1 forcible
HT.2 Heat Stage 2 Run Hours xxxxx.xx hours HR_HTR_2 forcible
PE.1 Power Exhaust1 Run Hours xxxxx.xx hours HR_PE_1 forcible
PE.2 Power Exhaust2 Run Hours xxxxx.xx hours HR_PE_2 forcible
ALRM Alarm Relay Run Hours xxxxx.xx hours HR_ALM forcible
CRC Reheat1 Valve Run Hours xxxxx.xx hours HR_CRC forcible
RH2.A Reheat2 Valve A Run Hrs xxxxx.xx hours HR_RH2_A forcible
RH2.B Reheat2 Valve BC Run Hrs xxxxx.xx hours HR_RH2_B forcible
STRT Component Starts
A1 Compressor A1 Starts xxxxxx ST_A1 forcible
A2 Compressor A2 Starts xxxxxx ST_A2 forcible
B1 Compressor B1 Starts xxxxxx ST_B1 forcible
C1 Compressor C1 Starts xxxxxx ST_C1 forcible
CCH Crankcase Heat Starts xxxxxx ST_CCH forcible
IDF Indoor Fan Starts xxxxxx ST_IDF forcible
OFC.1 Outdoor Fan 1 Starts xxxxxx ST_OFC_1 forcible
OFC.2 Outdoor Fan 2 Starts xxxxxx ST_OFC_2 forcible
OFC.3 Outdoor Fan 3 Starts xxxxxx ST_OFC_3 forcible
HT.1 Heat Stage 1 Starts xxxxxx ST_HTR_1 forcible
HT.2 Heat Stage 2 Starts xxxxxx ST_HTR_2 forcible
PE.1 Power Exhaust 1 Starts xxxxxx ST_PE_1 forcible
PE.2 Power Exhaust 2 Starts xxxxxx ST_PE_2 forcible
ALRM Alarm Relay Starts xxxxxx ST_ALM forcible
CRC Reheat1 Valve Starts xxxxxx ST_CRC forcible
RH2.A Reheat2 Valve A Starts xxxxxx ST_RH2_A forcible
RH2.B Reheat2 Valve BC Starts xxxxxx ST_RH2_B forcible
(ALRMDISP) = CCN
only)
ALRMDISP
Active Alarm 1 Code xxx ALMCODE1
Active Alarm 2 Code xxx ALMCODE2
Active Alarm 3 Code xxx ALMCODE3
Active Alarm 4 Code xxx ALMCODE4
Active Alarm 5 Code xxx ALMCODE5
Reset All Current Alarms Yes/No ALRESET forcible
Reset Alarm History Yes/No ALHISCLR forcible
48/50PG and PM