199
Accessory/FIOP Static Pressure Drops (in. wg)* -- 48/50PM16-- 28
CFM Economizer Humidi---MiZer™ (16, 20, 24) H u m i d i --- M i Z e r ™ ( 2 8 )
4000 0.02 0.17 ---
4500 0.03 0.19 ---
5000 0.04 0.21 ---
5500 0.05 0.24 ---
6000 0.06 0.27 ---
6500 0.07 0.31 0.19
7000 0.08 0.35 0.21
7500 0.09 0.39 0.23
8000 0.1 0.43 0.26
8500 0.11 0.48 0.29
9000 0.12 0.52 0.31
9500 0.13 0.57 0.34
10000 0.15 0.62 0.37
10500 0.16 --- 0.4
11000 0.17 --- 0.43
11500 0.19 --- 0.46
12000 0.2 --- 0.5
LEGEND
FIOP --- Fa ct o r y --- I n s t a l l ed O pt i o n
* The static pressure must be added to the external static pressure. The sum and the evaporator entering ---air cfm should then be used in conjunction with the
Fan Performance tables to determine blower rpm and watts.
Accessory/FIOP Electric Heat Static Pressure Drop (in. wg) -- 50PM16--28 and 50PG20--28
CFM
Nominal Heater
Size (kw)
Pressure Drop (in.
wg)
Nominal Heater
Size (kw)
Pressure Drop (in.
wg)
Nominal Heater
Size (kw)
Pressure Drop (in.
wg)
4800
25
0.01
50
0.02
75
0.03
5000 0.01 0.02 0.04
6000 0.02 0.04 0.06
7000 0.03 0.06 0.08
8000 0.04 0.08 0.12
9000 0.05 0.1 0.15
10000 0.06 0.13 0.2
11500 0.09 0.18 0.27
LEGEND
FIOP --- Fa ct o r y --- I n s t a l l ed O pt i o n
NOTES:
1. Heaters are rated at 240v, 480v, and 600v.
2. The static pressure must be added to the external static pressure. The
sum and the evaporator entering---air cfm should then be used in
conjunction with the Fan Performance tables to determine blower rpm, bhp,
and watts.