CONTROL SET POINT AND CONFIGURATION LOG
Model Number: _____________________________
Serial Number: ______________________________
Date: ______________________________________
Technician: _________________________________
Software Versions: ___________________________
MBB: CESR131320 ---- _ _
ECB: CESR131249---- _ _
MARQ: CESR131171---- _ _
INDICATE UNIT SETTINGS BELOW
Control Type: Thermostat/T55 Space Temp./T-- 56 Space Temp./T-- 58 Space Temp.
Set Points: Cooling Occupied: _______________ Unoccupied: __________________
Heating Occupied: _______________ Unoccupied: __________________
MODE CONFIGURATION
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
S U B --- T A B L E
CCN POINT ENTRY
CONFIGURATION SERVICE
CONFIGURATION
DISP Display Configuration DISPLAY
METR Metric Display On/Off Off DISPUNIT
LANG Language Selection 0=English
1=Spanish
2=French
3=Portuguese
0 LANGUAGE
PROT Password Enable Enable/Dis-
able
Enable PASS_ EBL
PSWD Service P assword 0000 to 9999 1111 PASSWORD
TEST Test Display LEDs On/Off Off (display only, not in
table)
DISPTEST
UNIT Unit Configuration UNIT
S.DLY Startup Delay 0 to 600 sec 30 STARTDLY
U.CTL Unit Control Type 2=Thermostat
3=Space
Sensor
2 CTL_TYPE
T. CT L Thermostat Control Type 0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
3=Digital
0 ST ATTYPE
OC.FN FanOnWhenOccupied Yes/No Yes OCC_FAN
IDF.F Shut Down on IDF Failure Yes/No Ye s FATALFAN
FN.SW Fan Status Switch 0=No Switch
1=Normal
Open
2=Normal
Closed
0: no FIOP
1: FIOP
FANSTCFG
FL.SW Filter Status Switch 0=No Switch
1=Normal
Open
2=Normal
Closed
0: no FIOP
1: FIOP
FILSTCFG
FS.SW Fire Shutdown Switch 0=No Switch
1=Normal
Open
2=Normal
Closed
0: no FIOP
1: FIOP
SHTDNCFG
RM.SW Remote Occupancy
Switch
0=No Switch
1=Normal
Open
2=Normal
Closed
0 REMOCCFG
SAT.T SAT Settling Time 10 to 900 sec 240 SAT_SET
RAT.S RAT Sensor on SPTO In-
put
Yes/No No RAT_SPTO
RH.S RH Sensor on OAQ Input Yes/No No RH_OAQ
RH.SW Space Humidity Switch 0=No Switch
1=Normal
Open
2=Normal
Closed
0 : n o H u m i d i --- Mi Z e r
FIOP
1 : H u m i d i --- M i Z e r
FIOP
HUMSTCFG
TCS.C Temp Cmp Strt Cool
Factr
0to60 mins 0 TCSTCOOL
TCS.H Te mp C m p St r t H e at
Factr
0to60 mins 0 TCSTHEAT
48/50PG and PM