APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — CONFIGURATION
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
S U B --- T A B L E
CCN POINT PAGE NO.
CONFIGURATION
SERVICE
CONFIGURATION
DISP Display Configuration DISPLAY
METR Metric Display On/Off Off DISPUNIT 14
LANG Language Selection 0=English
1=Spanish
2=French
3=Portuguese
0 LANGUAGE 14
PROT Password Enable Enable/Disable Enable PASS_EBL 14
PSWD Service P assword 0000 to 9999 1111 PAS SWORD 14
TEST Test Display LEDs On/Off Off
(display only, not in
table)
DISPTEST 14
UNIT Unit Configuration UNIT
S.DLY Startup Delay 0 to 600 sec 30 STARTDLY 14
U.CTL Unit Control Type
2=Thermostat
3=Space
Sensor
2 CTL_TYPE 14
T. CT L Thermostat Control Type
0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
3=Digital
0 ST ATTYPE 15
OC.FN FanOnWhenOccupied Yes/No Yes OCC_FAN 15
IDF.F Shut Down on IDF Failure Yes/No Yes FATALFAN 15
FN.SW Fan Status Switch
0=No Switch
1=Normal
Open
2=Normal
Closed
0: no FIOP
1: FIOP
FANSTCFG 15
FL.SW Filter Status Switch
0=No Switch
1=Normal
Open
2=Normal
Closed
0: no FIOP
1: FIOP
FILSTCFG 15
FS.SW Fire Shutdown Switch
0=No Switch
1=Normal
Open
2=Normal
Closed
0: no FIOP
1: FIOP
SHTDNCFG 15
RM.SW
Remote Occupancy
Switch
0=No Switch
1=Normal
Open
2=Normal
Closed
0 REMOCCFG 15
SAT.T SAT Settling Time 10 to 900 sec 240 SAT_SET 15
RAT.S
RAT Sensor on SPTO In-
put
Yes/No No RAT_SPTO 15
RH.S RH Sensor on OAQ Input Yes/No No RH_OAQ 15
RH.SW Space Humidity Switch
0=No Switch
1=Normal
Open
2=Normal
Closed
0 : n o H u m i d i --- Mi Z e r
FIOP
1 : H u m i d i --- M i Z e r
FIOP
HUMSTCFG 15
TCS.C
Temp Cmp Strt Cool
Factr
0to60 mins 0 TCSTCOOL 15
TCS.H
Te m p C m p St r t H e at
Factr
0to60 mins 0 TCSTHEAT 15
48/50PG and PM