APPENDIX A LOCAL DISPLAY AND CCN TABLES (CONT)
MODE OPERATING MODES (cont)
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S U B --- T A B L E
CCN POINT
CCN WRITE
STATUS
DISPLAY
WRITE
STATUS
DMD.L DEMAND LIMITING DMDL
DMC.L Demand Limit In Effect Yes/No MODEDMDL
LMT.C Max Cool Stage In Effect x CSTGLIMT
LMT.H Max Heat Stage In Effect x HSTGLIMT
REDL Redline Activated Yes/No MODEREDL
SHED Loadshed Activated Yes/No MODESHED
MAX.C Max Allowed Cool Stages x MAXCSTGS
MAX.H Max Allowed Heat Stages x MAXHSTGS
( D i s p l a y T R I M --- s e e
Configuration)
Sensor Calibration TRIM
Space Temp Calibration
--- 3 0 t o
130
dF SPT_CAL forcible
Space Temp T rim --- 30 to 30 ^F SPT_OFF forcible
Supply Air Temp Calib.
--- 3 0 t o
130
dF SAT_CAL forcible
Supply Air Temp Trim --- 30 t o 30 ^F SAT_OFF forcible
Return Air Temp Calib.
--- 3 0 t o
130
dF RAT_CAL forcible
Return Air Temp Trim --- 30 to 30 ^F RAT_OFF forcible
(LINKDATA = CCN
only)
CCN --- Linkage LINKDATA
Supervisory Element # xxx S U P E --- A D R
Supervisory Bus xxx S U P E --- B U S
Supervisory Block Number xxx BLOCKNUM
Average Occup. Heat Stp. xxxx.x dF AOHS
Average Occup. Cool Stp. xxxx.x dF AOCS
Average Unocc. Heat Stp. xxxx.x dF AUHS
Average Unocc. Cool Stp. xxxx.x dF AUCS
AverageZoneTemperature xxxx.x dF AZT
Average Occup. Zone Temp xxxx.x dF AOZT
Linkage System Occupied? Yes/No LOCC
Next Occupied Day
”Mon”,
”Tue”, ,
”Sun”
3 --- c h a
rtext
LNEXTOCD
Next Occupied Time xx:xx
hh:m
m
LNEXTOCC forcible
Next Unoccupied Day
”Mon”,
”Tue”, ,
”Sun”
3 --- c h a
rtext
LNEXTUOD
Next Unoccupied Time xx:xx
hh:m
m
LNEXTUNC forcible
Last Unoccupied Day
”Mon”,
”Tue”, ,
”Sun”
3 --- c h a
rtext
LLASTUOD
Last Unoccupied Time xx:xx
hh:m
m
LLASTUNC forcible
(OCCDEFM = CCN
only)
Occupancy Supervisory OCCDEFM
Current Mode (1=Occup) 0,1 MODE
CurrentOccupPeriod# 0to8 PER_NO
T i m e --- O v e r r i d e i n E f f e c t Yes/No OVERLAST
Time--- Override Duration 0to4 hours OVR_HRS
Current Occupied Time xx.xx
hh:m
m
STRTTIME
Current Unoccupied Time xx.xx
hh:m
m
ENDTIME
Next Occupied Day NXTOCDAY
Next Occupied Time xx.xx
hh:m
m
NXTOCTIM
Next Unoccupied Day NXTUNDAY
Next Unoccupied Time xx.xx
hh:m
m
NXTUNTIM
Previous Unoccupied Day PRVUNDAY
Previous Unoccupied Time xx.xx hh.mm PRVUNTIM
MODE ALARMS
ITEM EXPANSION RANGE DEFAULT
CCN TABLE/
S U B --- T A B L E
CCN
POINT
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
MAINTENANCE DISPLAY
ALARMS ALARMS
R.CUR Reset All Current Alarms Ye s/ No No ALRESET forcible forcible
R.HIS Reset Alarm History Ye s/No No ALHISCLR forcible forcible
CURR Currently Active Alarms
alarm# text string
ALARM01C
---
ALARM25C
(repeat up to 25
alarms)
HIST Alarm History ALARM HISTORY
alarm#
a l a rm# --- m m / d d / y y ---
hh.mm--- text string
(repeat up to 20
alarms)
48/50PG and PM