159
Fan Performance — 50PG16 Horizontal Units
Airflow
(Cfm)
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
4500 592 0.87 670 1.16 732 1.43 787 1.70 837 1.97
4800 619 1.01 696 1.32 758 1.62 812 1.91 861 2.20
5100 647 1.17 723 1.50 784 1.82 838 2.13 886 2.44
5400 675 1.34 750 1.70 810 2.04 863 2.37 911 2.70
5700 704 1.54 776 1.91 837 2.27 889 2.63 936 2.97
6000 733 1.75 804 2.14 863 2.53 915 2.91 962 3.27
6300 762 1.99 831 2.40 890 2.80 941 3.20 988 3.59
6600 792 2.25 858 2.67 917 3.10 968 3.52
1014 3.93
6900 822 2.53 886 2.97 944 3.42 994 3.86 1040 4.29
7200 852 2.84 914 3.29 971 3.76 1021 4.22 1066 4.68
7500 882 3.17 942 3.63 998 4.12 1048 4.61 1093 5.09
Airflow
(Cfm)
Available External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
4500 884 2.25 929 2.52 972 2.80 1014 3.09 1054 3.38
4800 907 2.49 951 2.78 992 3.07 1033 3.37 1072 3.68
5100 931 2.74 973 3.05 1014 3.36 1053 3.68
1091 3.99
5400 955 3.02 997 3.35 1036 3.67 1075 4.00 1112 4.33
5700 980 3.32 1021 3.66 1060 4.00 1097 4.35 1133 4.70
6000 1005 3.64 1045 4.00 1084 4.36 1120 4.72 1156 5.08
6300 1030 3.98 1070 4.35 1108 4.73 1144 5.11 1179 5.49
6600 1056 4.34 1095 4.74 1133 5.13 1168 5.53 1203 5.93
6900 1082 4.72 1121 5.14 1158 5.56 1193 5.97 1227 6.39
7200 1108 5.13 1147 5.57 1183 6.00 1218 6.44 1252 6.87
7500 1134 5.56 1173 6.02 1209 6.48 1244 6.93 1277 7.38
LEGEND
B h p --- Brake Horsepower
Mid--- Low Range Motor/Drive Required
High Range Motor/Drive Required
NOTES:
1. Motor drive range is 710 to 879 for low range motor/drive, 872 to 1066 rpm for
mid --- low range motor/drive, and 1066 to 1260 rpm for high range motor/drive. All other
rpms require a field-supplied drive.
2. Maximum continuous bhp is 3.70 for low range motor/drive, 5.25 for mid---low range
motor/drive, and 7.50 for high range motor/drive.
3. See General Fan Performance Notes.
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
1. Static pressure losses from accessories and options
(Humidi-MiZer™ system, economizer, etc.) must be added
to external static pressure before entering Fan Performance
table. Refer to Accessory/FIOP Static Pressure information.
2. Interpolation is permissible. Do not extrapolate.
3. Fan performance tables are based on wet coils, clean filters,
and casing losses. Gas heat losses are included for 48 series
units.
4. Extensive motor and drive testing on these units ensures
that the full horsepower range of the motor can be utilized
with confidence. Using the fan motors up to the bhp rating
shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.
5. Use of a field-supplied motor may affect wire size.
Recalculate the unit power supply MCA and MOCP if
required. Contact your Carrier representative for details.
6. Use the following formula to calculate input watts:
Input Watts = Bhp x (746/Motor Eff)
48/50PG and PM