202
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
S U B --- T A B L E
CCN POINT ENTRY
COOL (cont) Cooling Configuration COOL_CFG
CIR.B Circuit B
CB.LO CircuitBLockoutTemp 0 to 100F dF 0 : n o H u m i d i --- M i Z e r
FIOP
H u m i d i --- M i Z e r
FIOP:
40 (PG08--- 16)
0 (20--- 28, PM16)
OATLCMPB
CS.B1 Current Sensing B1 Enable/Dis-
able
Disable (03---07)
E n a b l e ( 0 8 --- 2 8 )
B1_SENSE
B1.FN Level 1 Fans B 0to7 n o H u m i d i --- M i Z e r
FIOP:
0 (03--- 07)
1 (PG08--- 16)
4 (20--- 28, PM16)
H u m i d i --- M i Z e r
FIOP:
0 (PG03--- 16)
1 (20--- 28, PM16)
CIR_B_1
B2.FN Level 2 Fans B 0to7 n o H u m i d i --- M i Z e r
FIOP:
0 (03--- 07)
3 (PG08--- 16)
6 (20, PM16)
2 (24--- 28)
H u m i d i --- M i z e r F I O P :
0 (03--- 14)
1 (PG16)
3 (20, PM16)
2 (24--- 28)
CIR_B_2
B3.FN Level 3 Fans B 0to7 n o H u m i d i --- M i Z e r
FIOP:
0 (03--- 07)
3 (PG08--- 16)
6 (20--- 28, PM16)
H u m i d i --- M i Z e r
FIOP:
0 (03--- 14)
1 (PG16)
3 (20--- 28, PM16)
CIR_B_3
CIR.C Circuit C
CC.LO CircuitCLockoutTemp 0 to 100F dF 0 OATLCMPC
CS.C1 Current Sensing C1 Enable/Dis-
able
Disable
Enable (PG16)
C1_SENSE
C1.FN Level 1 Fans C 0 --- 7 n o H u m i d i --- M i Z e r
FIOP:
0 (03--- 14)
1 (PG16)
0 (20--- 28, PM16)
H u m i d i --- M i Z e r
FIOP:
0 (03--- 16)
1 (20--- 28, PM16)
CIR_C_1
C2.FN Level 2 Fans C 0to7 n o H u m i d i --- Mi Z e r
FIOP:
0 (03--- 14)
3 (PG16)
0 (20--- 28, PM16)
H u m i d i --- M i Z e r
FIOP:
0 (03--- 14)
1 (PG16)
2 (20--- 28, PM16)
CIR_C_2
C3.FN Level 3 Fans C 0to7 n o H u m i d i --- Mi Z e r
FIOP:
0 (03--- 14)
3 (PG16)
0 (20--- 28, PM16)
H u m i d i --- M i Z e r
FIOP:
0 (03--- 14)
1 (PG16)
3 (20--- 28, PM16)
CIR_C_3
SST Low Suction Control
SST.O Suction OK Temperature 10 to 50 dF 18 SSTOK
SST.1 Low Suction --- Level 1 10 to 50 dF 20 SSTLEV1
SST.2 Low Suction --- Level 2 5to50 dF 15 SSTLEV2
SST.3 Low Suction --- Level 3 0to50 dF 10 SSTLEV3
CK.DL Delay On Low SST Check 0 to 300 sec 0 : n o H u m i d i --- Mi Z e r
FIOP:
40: Humidi--- MiZer
FIOP:
SSTCKDLY