MODE CONFIGURATION (cont)
ITEM EXPANS I O N RANGE UNITS DEFAULT
CCN TABLE/
Sub--- TABLE
CCN POINT ENTRY
I.FAN IND OOR FAN CONFIG FAN_CFG
FTYP Indoor F an Type 0 = 1 --- S P E E D
1=LEN VFD
2=ECM
3=DI VFD
4=AI VFD
0
1: SAV option
FAN_TYPE
NSPD Numb er of Speeds 2=TWO
3=THREE
7=SEVEN
2 NUM_SPDS
OC.FN FanOnWhenOccupied No/Y es Yes OCC_FAN
IDF.F Shut Down on IDF Failure No/Y es Yes FATALFAN
FS.MX S upply Fan Maximum
Speed
80 to 100 100 SPEEDMAX
FS.VN F an Speed --- V entilation 0 to 100 % 67 FSPDVENT
FS.AQ F an Speed --- IAQ Override 0 t o 100 % 100 FSPDAQOR
FS.E1 Fan Speed --- Free Cool Lo 0 to 100 % 67 FSPDECO1
FS.CL Fan Speed --- Mec h Cooli n g 60 to 100 % 67 FSPDCOOL
FS.RH Fan Sp eed --- Reheat2 65 to 100 % 100 FSPDREHT
S.VFD SUPPLY FAN VFD CONFIG
N.VLT VFD 1 Nom in al M otor V o lts 0 to 999 volts 208: 208/230v 1ph or 3ph
460: 460v
575: 575v
VFD1NVLT
N.AMP VFD1 Nom in al Motor Am p s 0 t o 999 amps Motor Dependent VFD1NAMP
N.FRQ VFD1 Nomi n al Motor Freq 10 t o 500 60 VFD1NFRQ
N.RPM VFD1 Nom inal Motor RPM 50 to 30000 Motor Dependent VFD1NRPM
N.PWR VFD1 Nomi n al Motor HPwr 0 to 500 Motor Dependent VFD1NPWR
M.DIR VFD1 Motor Dir ec tion 0=FORWARD
1=REVERSE
0 VFD1MDIR
ACCL VFD1 Acceleration Time 0 to 1800 secs 30 VFD1ACCL
DECL VFD1 Deceleration Time 0 to 1800 secs 30 VFD1DECL
SW.FQ VFD1 Switching Frequenc y 0to3 2 VFD1SWFQ
COOL Coolin g Con f i gu r ation COOL_C FG
N.CIR Number of Circuits 0to3 1 (03--- 07)
2 (08--- 28)
NUM_CIRC
MRT.C Compressor Min On Time 120 to 999 sec 180 MIN_ON
MOT.C Compressor Min Off Time 300 to 999 sec 300 MIN_OFF
RST.C Runtim e to Reset Strikes 120 to 999 sec 300 MIN_ON_S
C.DEC Cool Stag e Decreas e Tim e 120 to 999 sec 300 STAGEDEC
C.INC Cool Stage Incr eas e Tim e 120 t o 999 sec 450 ST AGEINC
FOD.C Fan---off Delay, Mech Cool 0 to 600 sec 60 COOL_FOD
ALM.N Alert Each Strike No/Yes Yes ALM_NOW
CA.LO CircuitALockoutTemp 0 t o 100F _F 40: no FIOP Low ambient
0: FIOP
OATLCMPA
CB.LO CircuitBLockoutTemp 0 to 100F _F 40: no FIOP Low ambient
0: FIOP
OATLCMPB
D.CMP Diagnose Comp Safety No/Yes No DIAGCOMP
MX.SA Max Suction Change CirA 0 to 100 PSIG 15 MAXDSSP A
MX.SB Max Suction Change CirB 0 to 100 PSIG 15 MAXDSSPB
SAT Supply Air Temperature
SA.PD SAT Cool Demand (+ ) Level 0.5 to 10 ^F 1 SAT_POS
SA.ND SA T Cool Dem and (--- ) Level --- 1 0 t o --- 0 . 5 ^F --- 1 SA T_NEG
SAT.U Min imu m SAT Upper Level 35.0 t o 65.0 _F 60 (03--- 14)
58 (17--- 24)
53 (28)
SATMIN_H
SAT.L Minim u m SAT Lower Lev el 35.0 to 65.0 _F 35 (03--- 07)
45 (08--- 14)
48 (17--- 28)
SATMIN_L
SPT Space Temperature
CL.PD SPT Cool Demand (+ ) Level 0.5 to 5 ^F 1 DEM_POS
CL.ND SPT Cool Deman d (---) Lev el --- 5 t o --- 0 . 5 ^F --- 1 DEM_NEG
C.LAG Cool Therm al Lag Fac tor 0to5 1 COOL_LAG
SST Low Suction Control
SST.O Suction OK Temperature 10 to 50 _F 18 SSTOK
SST.1 Low Suction -- - Level 1 10 to 50 _F 20 SSTLEV1
SST.2 Low Suction -- - Level 2 5to50 _F 15 SSTLEV2
SST.3 Low Suction -- - Level 3 0to50 _F 10 SSTLEV3
CK.DL Delay On Low SST Check 0 t o 300 sec 0 SSTCKDLY
ComfortLINK v1.X