INDOOR
AIRFLOW
AND
ADJUSTMENTS
Models
48KHA,KLA
end-discharge
units
have
direct-drive
blower
motors.
All
motors
are
factory-
connected
to
deliver
proper
heating
and
cooling
airflows
at
normal
external
static
pressures
(except
for
some
208-v
applications).
Table
5
shows
heating
airflow
at
various
tempera¬
ture
rises.
Table
6
shows
both
heating
and
cooling
airflows
at
various
external
static
pressures
for
Models
48KHA,KLA
direct-drive
units.
Refer
to
these
tables
to
determine
airflow
for
system
being
installed.
See
Table
8
for
rated
cooling
and
heating
airflows.
NOTE:
Be
sure
all
supply-
and
return-air
grilles
are
open,
free
from
obstructions
and
adjusted
properly.
NOTE:
When
operating
the
208/230-volt,
3-phase
versions
of
Models
48KHA048
and
48KHA060
at
208
volts,
lead
connections
of
blower
motor
must
be
changed
as
indicated
on
unit
wiring
label
to
ensure
proper
airflow.
Heating
and/or
cooling
airflow
of
208/230-v
direct-drive
blower
motors
can
be
changed
by
changing
the
lead
connections
of
blower
motor.
Motor
leads
are
color-coded
as
follows:
black
high
speed
blue
medium
speed
red
low
speed
NOTE:
Some
direct-drive
blower
motors
do
not
have
lead
for
medium
speed.
Factory
connections
and
available
optional
connections
are
shown
in
Table
6.
->
Table
8
Rated
Cooling
and
Heating
Airflows
MODEL
48-
COOLING
:
HEATING
Rated
Airflow
(cfm)*
ESP
(in.wg)
Rated
Airflow
(cfm)*
Maximum
ESP
(in.wg)*
KLA11831OBE
630
0
10
505
0.30
KLA124310BE
800
0
10
505
0
30
KHA02431OBF
800
0
10
947
0
30
KLA130310BE
1000
0
15
462
0
30
KHA03031OBF
1000
0
15
947
0.30
KLA136310BE
1200
0
15
758
0
30
KLA036510CE
;
1200
0
15
758
0
65
KLA03661OCE
1200
0
15
758
0.65
KHA136310BC
1200
0
15
1155
0
30
KHA036510CE
1200
0
15
1155
0
65
KHA03631OBF
1200
0
15
1445
0
30
KHA036510CF
1200
0
15
1445
0
65
KLA142310BE
1400
0
15
695
0
30
KLA042510CE
1400
0
15
695
0
65
KHA04231OBF
1400
0
15
1445
0
30
KHA042510CF
1400
0
15
1445
0
65
KLA148310BE
1600
0
20
925
0
30
KLA04851OCE
1600
0
20
925
0
65
KLA04861OCE
1600
0
20
925
0
65
KHA04831OBF
1600
0
20
1445
0
30
KHA048510CF
1600
0
20
1445
0.65
KLA160310BE
2000
0
20
1155
0
30
KHA06031OBF
2000
0
20
1735
0
30
ESP
External
Static
Pressure
*Rated
in
accordance
with
U
S
Government
D.O.E
test
pro¬
cedures
and/or
ARI
Standard
210-81
For
all
units,
motor
lead
connected
to
heat
relay
determines
heating
speed
and
resulting
airflow;
and
motor
lead
connected
to
cooling
relay
determines
the
cooling
speed
and
resulting
airflow.
See
unit
wiring
label.
To
change
heating
and/or
cooling
speed,
connect
appropriate
color-coded
lead
to
appropriate
relay.
Be
sure
to
properly
insulate
any
unused
motor
lead.
See
Make
Wiring
Connections,
Special
Procedures
for
208-v
Operation
section
for
proper
procedures
to
insulate
an
unused
electrical
lead.
When
installing
a
208-
or
230-v
direct-drive
unit
that
is
factory-connected
for
heating
and
cooling
speeds
that
are
not
the
same,
and
same
speed
for
both
heating
and
cooling
is
required
for
a
particular
application,
connect
appropriate
color-coded
lead
to
terminal
2
of
cooling
relay
and
connect
a
field-
supplied
jumper
between
heat
relay
and
terminal
2
of
cooling
relay.
Be
sure
to
properly
insulate
unused
motor
lead(s).
17