EasyManua.ls Logo

Carrier 48KLA - Ductwork Connections

Carrier 48KLA
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fig.
7
Sediment
Trap
5.
Install
an
accessible,
external,
manual
shutoff
valve
in
gas
supply
pipe
within
6
ft
of
heating
section.
NOTE:
The
unit
manual
shutoff
valve
has
a
1/8-in.
tapping
on
the
inlet
side
of
this
shutoff
for
measuring
gas
input
pressure.
6.
Install
ground-joint
union
close
to
heating
sec¬
tion
between
unit
manual
shutoff
and
external
manual
main
shutoff
valve.
7.
Pressure-test
all
gas
piping
in
accordance
with
local
and
national
plumbing
and
gas
codes
before
connecting
piping
to
unit.
NOTE:
When
pressure-testing
the
gas
supply
system
after
the
gas
supply
piping
has
been
con¬
nected
to
the
unit
gas
valve,
the
supply
piping
must
be
disconnected
from
the
gas
valve
during
any
pressure
testing
of
the
piping
systems
at
test
pressure
in
excess
of
0.5
in.
psig.
When
pressure
testing
the
gas
supply
piping
system
at
test
pres¬
sures
equal
to
or
less
than
0.5
in.
psig,
the
unit
heating
section
must
be
isolated
from
the
gas
piping
system
by
closing
the
external
main
manual
shutoff
valve
and
slightly
opening
ground-joint
union.
8.
W
here
permitted
by
local
codes,
use
an
approved
corrugated
metal
tubing
gas
connector
between
rigid
gas
piping
and
unit
manual
shutoff.
9.
C
heck
for
gas
leaks
at
all
field-installed
and
factory-installed
gas
lines
after
all
piping
connec¬
tions
have
been
completed.
Use
soap-and-water
solution
(or
method
specified
by
local
codes
and/
or
regulations).
Step
3
Make
Duct
Connections
Model
48KHA,KLA
has
duct
flanges
on
the
supply-and
return-air
openings
on
side
of
unit.
See
Fig.
4
for
connection
sizes
and
locations.
Adhere
to
the
following
requirements
when
se¬
lecting,
sizing
and
installing
duct
system:
1.
Select
and
size
ductwork,
supply-air
registers
and
return-air
grilles
according
to
ASHRAE
recom¬
mendations
and
as
presented
in
Carrier
System
Design
Manual,
Part
2.
2.
Use
a
flexible
transition
between
rigid
ductwork
and
unit
to
prevent
transmission
of
vibration.
The
transition
may
be
screwed
or
bolted
to
duct
flanges.
Use
suitable
gaskets
to
ensure
a
weather-
tight
and
airtight
seal.
->
Table
2
Filter
Sizes
(Field
Supplied),
(Sq
In.)*
MODEL
48-
STANDARD
DISPOSABLE
TYPE
CLEANABLE
OR
HIGH
CAPACITY
TYPE
KLA118310BE
302
202
KHA024310BF
454
303
KLA124310BE
384
257
KHA03031OBF
480
320
KLA130310BE
480
320
KHA03631OBF
694
462
KHA036510CE
576
384
KHA036510CF
694
462
KHA136310BE
576
384
,
KLA036510CE
576
384
KLA036610CE
576
384
KLA136310BE
576
384
KHA04231OBF
694
462
KHA04251OCF
694
462
KLA04251OCE
672
448
KLA142310BE
672
448
KHA04831OBF
768
512
KHA04851OCF
768
512
KLA04851OCE
768
512
KLA04861OCE
768
512
KLA148310BE
768
512
KHA060310BF
i
960
640
KLA160310BE
960
;
.
_J
640
^Required
air
filter
areas
shown
are
based
on
the
ARI-rated
cooling
airflow
or
the
heating
airflow
at
a
velocity
of
300
fpm
depending
on
whichever
value
is
larger
Air
filter
pressure
drop
should
not
exceed
0
08
in
wg
6