EasyManua.ls Logo

Carrier 48KLA - PERIODIC SERVICE AND MAINTENANCE

Carrier 48KLA
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CONTROLS
All
compressors
have
the
following
internal-protection
controls:
High-Pressure
Relief
Valve
This
valve
opens
when
pressure
differential
between
low
and
high
side
becomes
excessive.
Compressor
Overload
This
overload
interrupts
power
to
compressor
when
either
current
or
internal
temperature
becomes
excessive,
and
automatically
resets
when
internal
temperature
drops
to
a
safe
level.
This
overload
may
require
up
to
60
minutes
(or
longer)
to
reset;
therefore,
if
internal
overload
is
suspected
of
being
open,
disconnect
electrical
power
to
unit
and
check
circuit
through
overload
with
an
ohmmeter
or
continuity
tester.
COOLING
SEQUENCE
OF
OPERATION
The
following
sequence
of
operation
pertains
to
all
208/
230-volt,
3-phase
units;
however,
sequence
of
opera¬
tion
of
single-phase
and
460-volt
units
is
very
similar.
Refer
to
wiring
diagram
in
Fig.
10.
NOTE:
Although
actual
unit
wiring
may
vary
slightly
from
that
shown
in
Fig.
10,
sequence
of
operation
will
not
be
affected.
With
room
thermostat
selector
switch
in
the
COOL
position
and
fan
switch
in
AUTO,
position,
cooling
sequence
of
operation
is
as
follows:
When
room
temperature
rises
to
a
point
slightly
above
cooling
control
setting
of
thermostat,
thermo¬
stat
cooling
bulb
tilts
and
completes
circuit
between
thermostat
terminal
R
to
terminals
Y
and
G.
These
completed
circuits
through
the
thermostat
connect
contactor
coil
(through
unit
wire
Y)
and
relay
coil
(through
unit
wire
G)
across
the
24-volt
secondary
of
transformer.
The
2
sets
of
normally
open
contacts
of
energized
contactor
2D
close
and
complete
circuit
through
compressor
motor
3F
and
condenser
fan
motor
3D1.
Both
motors
start
instantly.
The
set
of
normally
open
contacts
of
energized
relay
closes
and
completes
circuit
through
evapo¬
rator
blower
motor.
Blower
motor
starts
instantly.
NOTE:
Three-phase
units
are
equipped
with
a
2-
speed
condenser
fan
motor
and
a
temperature-
actuated
switch.
Fan
motor
operates
at
high
speed
when
outdoor
temperature
rises
to
75
±
3
F
and
continues
to
operate
at
high
speed
until
outdoor
temperature
drops
to
61
±
4
F.
At
61
F
or
lower,
fan
motor
operates
at
low
speed
and
permits
cooling
operation
down
to
40
F.
Cooling
cycle
remains
on
until
room
temperature
drops
to
a
point
slightly
below
cooling
control
set¬
ting
of
room
thermostat.
At
this
point,
thermostat
cooling
bulb
tilts
and
breaks
circuit
between
thermo¬
stat
terminal
R
to
terminals
Y
and
G.
These
open
circuits
de-energize
contactor
coil
and
relay
coil.
Condenser,
compressor
and
blower
motors
stop.
Unit
is
in
a
standby
condition,
waiting
for
next
call
for
cooling
from
room
thermostat.
SERVICE
To
ensure
continuing
high
performance,
and
to
minimize
possibility
of
premature
equipment
failure,
periodic
maintenance
must
be
performed
on
this
equipment.
This
combination
heating/
cooling
unit
should
be
inspected
at
least
once
each
year
by
a
qualified
service
person.
NOTE
TO
EQUIPMENT
OWNER:
Consult
your
local
dealer
about
the
availability
of
a
maintenance
contract.
The
minimum
maintenance
requirements
for
this
equipment
are
as
follows:
1.
Inspect
air
filter(s)
each
month.
Clean
or
replace
when
necessary.
2.
Inspect
cooling
coil,
drain
pan,
and
condensate
drain
each
cooling
season
for
cleanliness.
Clean
when
necessary.
3.
Inspect
blower
motor
and
wheel
for
cleanliness
and
check
lubrication
each
heating
and
cooling
season.
Service
when
necessary.
4.
Check
electrical
connections
for
tightness
and
controls
for
proper
operation
each
heating
and
cooling
season.
Service
when
necessary.
5.
Check
and
inspect
heating
section
before
each
heating
season.
Clean
and
adjust
when
necessary.
18

Related product manuals