EasyManua.ls Logo

Carrier 48KLA - TROUBLESHOOTING HEATING ISSUES; Heating Service Analysis Chart

Carrier 48KLA
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TROUBLESHOOTING
CHART
Table
9
Heating
Service
Analysis
Chart
SYMPTOM
!
PROBABLE
CAUSE
REMEDY
Pilot
will
not
light
No
spark
at
electrode
Check
air
gap
between
electrode
tip
and
pilot
burner
Gap
should
be
as
shown
in
Fig.
11
Readjust
as
necessary.
Clean
moisture
or
dirt
accumulation
on
electrode
ceramic
with
cloth.
Cracked
ceramic
replace
pilot
electrode
assembly.
Check
for
loose
or
broken
wiring
at
and
between
spark
generator
and
electrode.
Replace
wire
or
tighten
con¬
nection
as
necessary.
Check
fuses
or
circuit
breaker
to
ensure
voltage
to
unit.
Check
24-volt
input
to
spark
generator.
If
reading
is
24
volts,
and
above
steps
have
been
completed,
replace
electronic
control
head
portion
of
control
head/gas
valve
assembly.
Spark
shorting
out
to
main
burner
Realign
electrode
tip
away
from
main
burner
but
main¬
tain
spark
gap
to
pilot
burner.
See
Fig
11.
No
gas
at
pilot
burner
Clean
pilot
orifice.
Check
for
24
volts
between
terminals
no.
1
and
GR
of
gas
valve.
If
reading
is
24
volts,
and
above
steps
have
been
completed,
replace
gas
valve
portion
of
control
head/gas
valve
assembly.
Burners
will
not
ignite
:
i
Water
in
gas
line
Drain
install
water
trap.
No
power
to
furnace
Check
power
supply,
fuses,
wiring,
or
circuit
breaker.
No
24-volt
power
supply
to
control:
circuit
i
Check
transformer
replace
if
necessary
Miswired
or
loose
connections
Check
all
wiring
and
wirenut
connections.
Dirty
pilot
yellow
flame
Clean
pilot
orifice
Pilot
burning
improperly
sharp
blue
flame
Replace
pilot.
Burned-out
heat
anticipator
in
thermostat
Replace
thermostat
No
gas
at
main
burners
1.
Check
for
24
volts
between
terminals
3
and
GR
on
control
head
If
reading
is
24
volts,
replace
gas
valve
portion
of
control
head/gas
valve
assembly.
2
If
reading
is
not
24
volts,
check
flame
sensor
for
cracked
ceramic
insulator
or
shorted
sensor
cable.
Replace
electronic
head
if
sensor
circuit
is
not
defective.
Broken
thermostat
wire
Run
continuity
check
to
locate
break.
Inadequate
heating
Dirty
air
filter
Clean
or
replace
filter
as
necessary
Gas
input
to
furnace
too
low
Check
gas
pressure
at
manifold.
Clock
gas
meter
for
input
If
too
low,
increase
manifold
pressure,
or
replace
with
correct
orifices
Unit
undersized
for
application
Replace
with
proper
unit
or
add
additional
unit.
Restricted
airflow
Clean
or
replace
filter
or
remove
any
restriction.
Blower
speed
too
low
;
Use
faster
speed
tap
or
install
optional
blower.
Limit
switch
cycles
main
burners
Dirty
air
filters
clean
or
replace
Registers
closed,
restricted
ductwork—
open
or
remove
restriction.
Check
heat
anticipator
setting
on
thermostat
readjust.
Poor
flame
characteristics
Incomplete
combustion
results
in
Aldehyde
odors,
(CO),
sooting'
flame
floating
flame
Air
shutters
on
burners
closed
adjust
to
soft
blue
flame
Check
all
screws
around
flue
outlets
and
burner
com¬
partment
tighten
Lack
of
combustion
air
See
Installation
section.
Cracked
heat
exchanger
replace.
Overfired
furnace
reduce
input,
or
change
orifices.
Check
vent
for
restriction
clean
as
required.
Check
orifice
to
burner
alignment
22

Related product manuals