Table 1A — Physical Data — 48TF004-007 (cont)
LEGEND
*Evaporator coil fin material/condenser coil fin material. Contact your local
representative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
††Rollout switch lockout is manually reset by interrupting power to unit or
resetting thermostat.
||48TFG, TFH, and TFK units are California compliant three-phase high heat
models.
***Three-phase standard high heat models have heating input values as
shown. Single-phase standard high heat models have one-stage heating
with heating input values as follows:
48TFF004 — 115,000 Btuh
48TFF005,006 — 150,000 Btuh
†††California SCAQMD compliant Low NO
x
models have combustion prod-
ucts that are controlled to 40 nanograms per joule or less.
¶Steady State Efficiency is 80% on all units except 48TFK004, which is
81%.
NOTE: High-static motor not available on single-phase units.
UNIT SIZE 48TF E/F/H/K/M/N004 D/E/F/G/H/K/L/M/N005 D/E/F/G/H/K/L/M/N006 D/E/F007
FURNACE SECTION
Rollout Switch Cutout
Temp (F)† 195 195 195 195
Burner Orifice Diameter
(in. ...drill size)
Natural Gas Std TFD/GII .113...33 .113...33 .113...33
TFE/HII .113...33 .113...33 .113...33 .113...33
TFF/KII .113...33 .129...30 .129...30 .129...30
TFL .102...38 .102...38
TFM .102...38 .102...38 .102...38
TFN .102...38 .116...32 .116...32
Liquid Propane Alt TFD/GII .089...43 .089...43 .089...43
TFE/HII .089...43 .089...43 .089...43 .089...43
TFF/KII .089...43 .104...37 .104...37 .104...37
TFL .082...45 .082...45
TFM .082...45 .082...45 .082...45
TFN .082...45 .094...42 .094...42
Thermostat Heat Anticipator
Setting (amps)
208/230 v and 575 Stage 1 .14 .14 .14 .14
Stage 2 .14 .14 .14 .14
460 v Stage 1 .14 .14 .14 .14
Stage 2 .14 .14 .14 .14
Gas Input (Btuh) Standard Units TFD —/74,000 —/74,000 —/74,000
(Stage 1/Stage 2) TFE —/74,000 —/115,000 —/115,000 —/115,000
TFF*** 82,000/115,000 120,000/150,000 120,000/150,000 120,000/150,000
No NOx Units TFGII 72,000 72,000
TFHII 72,000 115,000 115,000
TFKII 115,000 150,000 150,000
Low NOx Units TFL††† 60,000 60,000
TFM††† 60,000 90,000 90,000
TFN†† 90,000 120,000 120,000
Efficiency (Steady
State) (%) 80808080
Temperature Rise Range TFD/GII 25-55 25-55 25-55
TFE/HII 25-55 35-65 35-65 35-65
TFF/KII 55-85 50-80 50-80 50-80
TFL 20-50 20-50
TFM 20-50 30-60 30-60
TFN 30-65 40-70 40-70
Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 3.5
Liquid Propane Alt 3.5 3.5 3.5 3.5
Gas Valve Quantity 1111
Gas Valve Pressure Range
Psig 0.180-0.487 0.180-0.487 0.180-0.487 0.180-0.487
in. wg 5.0-13.5 5.0-13.5 5.0-13.5 5.0-13.5
Field Gas Connection
Size (in.)
1
/
2
1
/
2
1
/
2
1
/
2
HIGH-PRESSURE SWITCH (psig)
Standard Compressor 450 ± 50 500 ± 50
Internal Relief (Differential)
Cutout 428 428
Reset (Auto.) 320 320
LOSS-OF-CHARGE (LOW-
PRESSURE SWITCH) (psig)
7 ± 3
Cutout
Reset (Auto.) 22 ± 7
FREEZE PROTECTION
THERMOSTAT (F)
Opens 30 ± 5
Closes 45 ± 5
OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (in.) 1...20 x 24 x 1
RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 2...16 x 25 x 2