6
Table 1A — Physical Data — 48TF004-007 (cont)
LEGEND
*Evaporator coil fin material/condenser coil fin material. Contact your local
representative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
††Rollout switch lockout is manually reset by interrupting power to unit or
resetting thermostat.
||48TFG, TFH, and TFK units are California compliant three-phase high heat
models.
***Three-phase standard high heat models have heating input values as
shown. Single-phase standard high heat models have one-stage heating
with heating input values as follows:
48TFF004 — 115,000 Btuh
48TFF005,006 — 150,000 Btuh
†††California SCAQMD compliant Low NO
x
models have combustion prod-
ucts that are controlled to 40 nanograms per joule or less.
¶Steady State Efficiency is 80% on all units except 48TFK004, which is
81%.
NOTE: High-static motor not available on single-phase units.
UNIT SIZE 48TF E/F/H/K/M/N004 D/E/F/G/H/K/L/M/N005 D/E/F/G/H/K/L/M/N006 D/E/F007
FURNACE SECTION
Rollout Switch Cutout
Temp (F)†† 195 195 195 195
Burner Orifice Diameter
(in. ...drill size)
Natural Gas Std TFD/GII — .113...33 .113...33 .113...33
TFE/HII .113...33 .113...33 .113...33 .113...33
TFF/KII .113...33 .129...30 .129...30 .129...30
TFL — .102...38 .102...38 —
TFM .102...38 .102...38 .102...38 —
TFN .102...38 .116...32 .116...32 —
Liquid Propane Alt TFD/GII — .089...43 .089...43 .089...43
TFE/HII .089...43 .089...43 .089...43 .089...43
TFF/KII .089...43 .104...37 .104...37 .104...37
TFL — .082...45 .082...45 —
TFM .082...45 .082...45 .082...45 —
TFN .082...45 .094...42 .094...42 —
Thermostat Heat Anticipator
Setting (amps)
208/230 v and 575 Stage 1 .14 .14 .14 .14
Stage 2 .14 .14 .14 .14
460 v Stage 1 .14 .14 .14 .14
Stage 2 .14 .14 .14 .14
Gas Input (Btuh) Standard Units TFD — —/74,000 —/74,000 —/74,000
(Stage 1/Stage 2) TFE —/74,000 —/115,000 —/115,000 —/115,000
TFF*** 82,000/115,000 120,000/150,000 120,000/150,000 120,000/150,000
No NOx Units TFGII — 72,000 72,000 —
TFHII 72,000 115,000 115,000 —
TFKII 115,000 150,000 150,000 —
Low NOx Units TFL††† — 60,000 60,000 —
TFM††† 60,000 90,000 90,000 —
TFN††† 90,000 120,000 120,000 —
Efficiency (Steady
State) (%) 80¶808080
Temperature Rise Range TFD/GII — 25-55 25-55 25-55
TFE/HII 25-55 35-65 35-65 35-65
TFF/KII 55-85 50-80 50-80 50-80
TFL — 20-50 20-50 —
TFM 20-50 30-60 30-60 —
TFN 30-65 40-70 40-70 —
Manifold Pressure (in. wg)
Natural Gas Std 3.5 3.5 3.5 3.5
Liquid Propane Alt 3.5 3.5 3.5 3.5
Gas Valve Quantity 1111
Gas Valve Pressure Range
Psig 0.180-0.487 0.180-0.487 0.180-0.487 0.180-0.487
in. wg 5.0-13.5 5.0-13.5 5.0-13.5 5.0-13.5
Field Gas Connection
Size (in.)
1
/
2
1
/
2
1
/
2
1
/
2
HIGH-PRESSURE SWITCH (psig)
Standard Compressor 450 ± 50 500 ± 50
Internal Relief (Differential)
Cutout 428 428
Reset (Auto.) 320 320
LOSS-OF-CHARGE (LOW-
PRESSURE SWITCH) (psig)
7 ± 3
Cutout
Reset (Auto.) 22 ± 7
FREEZE PROTECTION
THERMOSTAT (F)
Opens 30 ± 5
Closes 45 ± 5
OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (in.) 1...20 x 24 x 1
RETURN-AIR FILTERS Throwaway
Quantity...Size (in.) 2...16 x 25 x 2
Al — Aluminum
Bhp — Brake Horsepower
Cu — Copper