13.
Fasten
hood
top
and
side
plate
assembly
(Fig.
9)
and
economizer
to
unit
with
screws
supplied.
Before
attaching,
make
sure
bottom
of
hood
assembly
is
resting
on
top
of
unit
base
rail.
14.
Place
knob
supplied
with
accessory
economizer
on
OAT.
See
Fig.
20.
Set
for
3
degrees
below
indoor
room
thermostat
setting.
If
accessory
enthalpy
control
(EC)
(Fig.
20)
is
used
in
lieu
of
OAT.,
refer
to
instructions
shipped
with
accessory
enthalpy
control
for
installation
and
adjustment.
15.
Connect
OAT./EC
and
CLS
per
unit
label.
See
Fig.
21.
Connect
2
economizer
wires
to
each
switch
with
quick-connects.
Unit
connecting
wires
are
shipped
taped
on
outdoor
blade.
See
Fig.
15.
16.
Slide
outdoor
air
inlet
screens
in
hood
screen
tracks.
Secure
screens
with
screen
retainer
across
hood
front.
Secure
screen
retainer
with
screw
provided.
See
Fig.
22.
17.
Replace
upper
filter
access
panel
with
screws
saved
from
step
2.
18.
Turn
base
unit
power
on.
CLS
CLS
Cooling
Lockout
Switch
EC
Enthalpy
Control
OAT.
Outdoor
Air
Thermostat
NOTE:
When
Enthalpy
Control
(EC)
is
installed,
outdoor
air
thermo¬
stat
(OAT
)
is
removed
from
economizer
Fig.
21
Wiring
Connections
for
Outdoor
Air
Thermostat/or
Enthalpy
Control
and
Cooling
Lockout
Switch
AIR
INLET
SCREEN
OUTDOOR
AIR
.BASE
UNIT
RETAINER
HOOD
/
Fig.
22
Economizer
and
Outdoor
Air
Hood
Assembled
to
Unit
START-UP
Unit
Preparation
Make
sure
unit
has
been
installed
in
accordance
with
installation
instruc¬
tions
and
applicable
codes.
Compressor
Mounting
Compressors
are
inter¬
nally
spring
mounted.
Do
not
loosen
or
remove
compressor
holddown
bolts.
Internal
Wiring
Check
all
electrical
connections
in
unit
control
boxes.
.
.tighten
as
required.
Refrigerant
Service
Valves
Each
unit
system
has
2
Schrader
type
service
ports,
one
on
the
suction
line
and
one
on
the
compressor
discharge
line.
Be
sure
that
caps
on
the
ports
are
tight.
Crankcase
Heater{s)
are
energized
as
long
as
there
is
power
to
the
unit.
Energize
heater(s)
24
hours
prior
to
base
unit
start-up.
Cooling
To
start
unit,
turn
on
main
power
supply.
Set
system
selector
switch
to
COOL
and
fan
switch
at
AUTO.
Adjust
thermostat
to
a
setting
below
room
temperature.
Compressor
starts
on
closure
of
contactor.
Check
cooling
effects
at
a
setting
above
room
temperature.
Check
unit
charge.
Refer
to
Refrig¬
eration
Charge
in
Service
section.
Reset
thermostat
at
a
position
above
room
tem¬
perature.
Compressor
will
shut
off.
TO
SHUT
OFF
UNIT
Set
system
selector
switch
at
OFF
position
or
reset
thermostat
at
a
position
above
room
temperature.
Units
are
equipped
with
Cycle-LOC
protection
device.
Unit
shuts
down
on
any
safety
trip,
and
indicator
light
on
thermostat
comes
on.
Check
reason
for
safety
trip.
Compressor
restart
is
accomplished
by
manual
reset
at
the
thermostat
by
turning
the
selector
switch
to
OFF
and
then
to
ON.
Heating
To
start
unit,
turn
on
main
power
supply.
Refer
to
Crankcase
Heaters.
Set
thermostat
at
HEAT
and
a
setting
above
room
temperature,
fan
at
AUTO.
First
stage
of
thermostat
energizes
the
first-stage
electric
heater;
second-stage
electric
heater
elements
if
installed.
Check
heating
effects
at
air
supply
grille(s).
TO
SHUT
OFF
UNIT
Set
system
selector
switch
at
OFF
or
set
heating
selector
lever
below
room
temperature.
Ventilation
(Continuous
Fan)
Set
fan
and
sys¬
tem
selector
switches
at
ON
and
OFF,
respectively.
Evaporator
air
fan
operates
continuously
to
provide
constant
air
circulation.
Economizer
Operation
(50CD008)
See
pages
9
thru
12
for
start-up
and
checkout
proce¬
dures.
If
unit
is
equipped
with
modulating
out¬
door
air
control
(economizer),
it
should
operate
as
follows:
COOLING
MODE
Evaporator
and
condenser
fans
and
compressor
energize
when
there
is
a
call
12