EasyManua.ls Logo

Carrier 50EJQ - Field Control Wiring; Power Wiring

Carrier 50EJQ
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
On 208/230-v units, transformer no. 1 is wired for 230-v.
If 208/230-v unit is to be run with 208-v power supply, the
transformer must be rewired as follows:
1. Remove cap from red (208-v) wire.
2. Remove cap from spliced orange (230-v) wire. Discon-
nect orange wire from black unit power wire.
3. Cap orange wire.
4. Splice red wire and black unit power wire. Cap wires.
IMPORTANT: Be certain unused wires are capped.
Failure to do so may damage the transformers.
FIELD CONTROL WIRING Install either a Carrier-
approved accessory thermostat or a CCN (Carrier Comfort
Network) compatible temperature sensor. A control box dia-
gram is shown in Fig. 12.
Thermostat Wiring Install a Carrier-approved accessory
thermostat assembly (per current price pages) according to
the installation instructions included with the accessory or
these instructions. Locate thermostat assembly on a solid wall
in the conditioned space to sense average temperature.
Route thermostat cable or equivalent single leads of
colored wire from subbase terminals to low-voltage connec-
tions as shown on unit label wiring diagram and in Fig. 13.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (Amer-
ican Wire Gage) insulated wire (35 C minimum). For 50 to
75 ft, use no. 16 AWG insulated wire (35 C minimum). For
over 75 ft, use no. 14 AWG insulated wire (35 C minimum).
All wire larger than no. 18 AWG cannot be directly con-
nected to the thermostat and will require a junction box and
splice at the thermostat.
Set heat anticipators settings to 0.1 for all voltages. Set-
tings may be changed slightly to provide a greater degree of
comfort for a particular installation.
Sensor Wiring The temperature sensor is wired into the
unit control board. See Fig. 14.
The unit is controlled with a T-55 or T-56 zone sensor.
Terminal T1 (T-55) or TH (T-56) on the sensor is connected
to T1 of the base module board. Terminal T2 (T-55) or COM
(T-56) on the sensor is connected to T2 on the base module
board. If a T-56 set point override sensor is used, the over-
ride connection SW on the sensor is connected to T3 on the
base module board.
If more than one sensor is being used and averaged, sen-
sors must be wired in multiples of 4 or 9. See Fig. 15.
Remote Field Control A switch closure across terminals
R and W1 on TB-3 will initiate the Occupied mode. This
can be done manually as well as through a field-supplied
timeclock.
LEGEND
EQUIP Equipment
GND Ground
MCM Thousand Circular Mils
NEC National Electrical Code
TB Terminal Block
NOTE: Maximum wire size for TB1 is 500 MCM.
Fig. 11 Field Power Wiring Connections
LEGEND
CB Circuit Breaker
DIP Dual In-Line Package
FU Fuse
GND Ground
IFC Indoor Fan Contactor
OFC Outdoor Fan Contactor
PEC Power Exhaust Controller
PES Power Exhaust Sequencer
TB Terminal Block
TRAN Transformer
Fig. 12 Control Box Diagram
Fig. 13 Field Control Thermostat Wiring
11

Related product manuals