The default offset set points for modulating power ex-
haust are shown in Table 8.
Table 8 Power Exhaust Default Set Points
STAGE
OFF-
SET
DIFFER-
ENTIAL
OFF
VOLTAGE
ON
VOLTAGE
OFF
STATIC
PRESSURE
(in. wg)
1 50% 3% 6.0 6.3 0.00
2 55% 3% 6.5 6.8 0.06
3 60% 3% 7.0 7.3 0.12
4 64% 3% 7.4 7.7 0.18
The differential set point is the difference between the
turn off point and the turn on point for each module. It also
is calibrated in terms of percent of input signal, and has a
range of 1% to 7%. The differential potentiometer is cali-
brated in 1% increments, and is factory set at approximately
3%. It is recommended to leave the set point at 3%, to mini-
mize cycling of the fans.
The offset and differential potentiometers have been
factory set for atmospheric pressure. Do not change these
settings until there is some experience with the building. In
most cases the factory settings will be satisfactory. How-
ever, if the building pressure is not being maintained as
desired, then some minor adjusting on a trial and error basis
can be made.
Direct Digital Controls DIP Switch Configura-
tion
The Direct Digital Control (DDC) board must be
configured for each application. The DDC board is config-
ured through the DIP switches located on the board. There
are 8 DIP switches which configure 8 different applications
of the DDC. See Table 9. DIP switch 1 is on the left of the
block. DIP switch 8 is on the right of the block. To open a
DIP switch, push the switch toward the side marked ‘OPEN’
on the rocker switch with a suitable tool (small-blade screw-
driver). To close a DIP switch, push the switch away from
the side marked 9OPEN9 on the rocker switch. Factory set-
tings are shown in Table 10.
The DIP switch configurations of the unit control soft-
ware are as follows:
Set DIP switch 1 to closed to configure the unit to operate
as a CV (constant volume) unit
DIP switch 2 configures the unit to use a space sensor or
a thermostat
DIP switch 3 configures the DDC for use with an elec-
tronic expansion board
DIP switch 4 is used to field test the unit
DIP switch 5 is used to specify the type of power exhaust
DIP switch 6 configures the Time Guardt override and,
when used with the field test function, sets the minimum
damper position
Set DIP switch 7 to closed to configure the unit indoor fan
for use with electric heat
Set DIP switch 8 to open to configure the unit for heat
pump operation
Table 9 DIP Switch Configuration
SETTING 1 2 3 4 5 6 7 8
OPEN
CCN or Sensors
Used
Expansion
Board
Field Test
ON
Modulated
Power
Exhaust
Time GuardT Override
ON
Gas Heat
Heat Pump
Operation
IN CONJUNCTION
WITH FIELD TEST
Set Minimum
Damper Position
CLOSED CV Thermostat
Base Control
Board Only
Field Test
OFF
Constant
Volume
Power
Exhaust
Time Guard Override
OFF
Electric Heat
Air Conditioner
Operation
LEGEND
CCN Carrier Comfort Network
CV Constant Volume
NOTES:
1. The OPEN side of the DIP switch is marked ‘‘OPEN.’’ When the
rocker switch is on the ‘‘OPEN’’ side of the switch, the switch is
OPEN.
2. DIP switch no. 7 is used for indoor fan control during heat opera-
tion. It should be set to closed.
3. When the unit is field-tested (DIP switch 4 to OPEN), the function
of DIP switch 6 changes and it is used to set the minimum damper
position.
Table 10 DIP Switch Factory Settings
UNIT 12345678
50EJQ,EWQ Closed Closed Closed Closed Closed Closed Closed Open