43
12 - FACTORY OPTIONS AND ACCESSORIES
Gas connection
Use the gas line connections only with EC certi ed components.
The PCH module is supplied complete with a dual gas valve, gas
stabiliser and lter. All components are tted inside the burner
housing.
To complete the installation, as required by current standards, an
anti-vibration joint and a gas valve must be tted.
Note: A EN216 certi ed gas lter with ltration level lower or equal
to 50 micron must be used, with no pressure stabiliser, a wide
range gas lter must be used since the lter supplied as standard,
upstream of the gas valve, has a limited area.
If the burner is not going to be used over a prolonged
period the gas supply valve must be closed.
Important: For a correct maintenance, connect the PCH module
by means of a seal and swivel gasket. Avoid using threaded
connected directly on the gas connection.
During the installation, tighten the external gas supply pipe but
without exceeding the tightening torque of 200 Nm (PCH080) or
300Nm (PCH130, PCH160 and PCH210).
Important: It is strictly prohibited to supply gas to the circuit with
pressure higher than 60 mbar. Such pressures could cause the
valve to break.
If pressure are higher than 60 mbar, a pressure reducer must be
installed at least 10 m away and no pressure stabiliser must be
tted between the pressure reducer and the heater, but leaving
the gas lter.
1 2 3 4 5 6 7 8
Included in the burner module To be carried out
by the installer
Gas settings data for GAS G25.3 - Cat. K (Netherlands), G25.1 - Cat. S (Hungary), G2.350 - Cat. Ls (Poland) and G27 - Cat. Lw [ex GZ41.5] (Poland)
can be found in the manufacturer’s installation and maintenance manual (APENGROUP), supplied with the unit.
Key:
1. Main burner gas solenoid valve
2. Pilot burner gas solenoid valve
3. Pressure stabiliser:
4. Safety gas solenoid valve
5. Gas lter (small section)
6. Anti-vibration joint
7. Gas lter (large section)
8. Gas valve
Gas supply: Ø 3/4’
PCH130, PCH160 & PCH210PCH080
Gas supply: Ø 1 1/2’
Gas type Gas settings
PCH080 PCH130
(2 x PCH65)
PCH160
(2 x PCH80)
PCH210
(2 x PCH105)
M
in.
Max.
Min.
Max.
Min.
Max.
Min.
Max.
G20
Cat. E-H
Air supply pressure mbar 20 [min 17-max 25]
Ø pilot nozzle mm 0,7
Gas consumption (15°C-1013mbar) m3/h 1,74 8,68 2 x 1,31 2 x 6,88 2 x 1,74 2 x 8,68 2 x 2,22 2 x 10,58
Carbon dioxide - CO
2
content % 8,7 9,1 8,7 9,1 8,7 9,1 8,5 9,1
Fumes temperature ºC 26,5 70 31 86 26,5 70 28 80
Fume mass ow rate (max.) kg/h 135 2 x 107 2 x 135 2 x 165
Gas butter y valve mm 12,2 11,0 12,2 15,8
G25
Cat. L-LL
Air supply pressure mbar 25 [min 17-max 30] (20 for Germany)
Ø pilot nozzle mm 0,7 (0,75 for Germany)
Gas consumption (15°C-1013mbar) m3/h 2,02 10,1 2 x 1,53 2 x 8,00 2 x 2,02 2 x 10,1 2 x 2,21 2 x 12,30
Carbon dioxide - CO
2
content % 8,6 8,9 8,8 9,2 8,6 8,9 8,8 9,0
Fumes temperature ºC 26 70 31 86 26 70 28 80
Fume mass ow rate (max.) kg/h --
Gas butter y valve mm Not necessary
G30
Cat. 3B-P
Air supply pressure mbar 30 [min 25-max 35] - 50 [min 42,5-max 57,5]
Ø pilot nozzle mm 0,51
Gas consumption (15°C-1013mbar) m3/h 1,49 6,80 2 x 1,03 2 x 5,39 2 x 1,49 2 x 6,80 2 x 1,70 2 x 8,30
Carbon dioxide - CO
2
content % 10,1 10,3 10,7 11,3 10,1 10,3 10,4 10,6
Fumes temperature ºC 26,5 70 31 86 26,5 70 28 80
Fume mass ow rate (max.) kg/h --
Gas butter y valve mm 7,0 6,5 7,0 9,3
G31
Cat. 3P
Air supply pressure mbar 30 [min 25-max 35] - 37 [min 25-max 45] - 50 [min 42,5-max 57,5]
Ø pilot nozzle mm 0,51
Gas consumption (15°C-1013mbar) m3/h 1,34 6,70 2 x 1,01 2 x 5,31 2 x 1,34 2 x 6,70 2 x 1,47 2 x 8,18
Carbon dioxide - CO
2
content % 9,3 9,6 9,4 9,6 9,3 9,6 9,5 9,8
Fumes temperature ºC 26,5 70 31 86 26,5 70 28 80
Fume mass ow rate (max.) kg/h 107 2 x 84 2 x 107 2 x 130
Gas butter y valve mm 7,0 6,5 7,0 9,3