44
12 - FACTORY OPTIONS AND ACCESSORIES
Country table - gas category:
(*) Consult the available burners with G2.350.
Conversion of burner gas type
Conversion to LPG
The gas burner is supplied already set for natural gas and with the 
kit for conversion to LPG, including: calibrated gas orifi ce plate; pilot 
nozzle; adhesive plate “Equipment converted...”.
The kit is not supplied in countries where conversion is prohibited.
To convert the unit, follow these instructions:
■ disconnect from power supply;
■ access the inside of the burner module by removing the 4 Allen 
M6 screws that secure the front panel;
Conversion to gas G25 - G25.1 - G25.3 - G27
Conversion for gasses from G20 to G25 or G25.1 or G25.3 or G27 
is allowed only in countries of category II2ELL3B/P [Germany], 
II2Esi3P [France], II2E3P [Luxembourg] and category II2HS3B/P 
[Hungary] and category II2ELwLs3B/P [Poland].
For countries in category II2EK3B/P [Netherlands] the unit is 
supplied already set up and regulated for G20 or G25.3.
Conversion from one type of gas to another can only be performed 
by authorised service centres.
Note: The conversion kit to G25 , G25.1 and G27 is only supplied 
on request. The conversion kit to G25 is included in the standard 
supply for France, Germany and Luxembourg.
Conversion to G25 and/or G25.1, G25.3, G27 where possible, 
consists in:
■ insertion of orifi ce plate (according to the gas type and the 
equipment model).
After the conversion, relight the burner and follow the steps 
explained for the conversion to LPG.
Finally, stick the nameplate “Equipment converted for gas G25....”
■ between the gas pipe and the Venturi, replace the gas orifi ce plate 
fi tted (natural gas) with the one supplied with the kit (for LPG);
■ replace the pilot nozzle (natural gas) with the one in the kit 
(LPG);
■ restore power supply and set the heater up for ignition;
■ while the start-up electrode is sparking, make sure there are 
no gas leaks.
When the burner is lit and working at maximum capacity, verify that:
■ the valve intake pressure corresponds to the value required for 
the type of gas that you are using;
■ the combustion analysis procedure is performed as described 
in paragraph “Analysis of combustion”;
■ the level of CO
2
 is within the limits indicated for the type of 
gas being used (tables in Paragraph “GAS connection”). If a 
diff erent value is detected, change it by turning the adjustment 
screw: screwing it down decreases the CO
2
 level, loosening it 
increases the level.
Note: The heater with LPG is set up for G31 gas. If the unit 
runs on G30 instead, it is necessary to verify and possibly 
adjust settings for CO
2
 as shown in the table in paragraph “Gas 
connection”.
■ that the gas valve Venturi pipe connector does not leak.
After converting and regulating the unit, replace the nameplate 
indicating “Equipment regulated for natural gas” with the one in the 
kit that indicates “Equipment converted ...”. 
Allen M6 screws
Allen M6 screws
Country Category Gas Pressure 
(mbar)
Gas Pressure 
(mbar)
Austria, Switzerland II2H3B/P G20 20 G30/G31 50
Belgium<70kW
I2E(S)
B,I3P
G20/G25 20/25 G31 37
Belgium>70kW
I2E(R)
B,I3P
G20/G25 20/25 G31 37
Germany II2ELL3B/P G20/G25 20 G30/G31 50
Denmark, Finland, 
Greece, Sweden, 
Norway, Italy, Czech 
Rep., Estonia, 
Lithuania, Slovenia, 
Albania, Macedonia, 
Bulgaria, Romania, 
Croatia, Turkey, 
Azerbaijan
II2H3B/P G20 20 G30/G31 30
Spain, United 
Kingdom, Ireland, 
Portugal, Slovakia
II2H3P G20 20 G31 37
France II2Esi3P G20/G25 20/25 G31 37
Luxembourg II2E3P G20/G25 20 G31 37/50
Netherlands II2EK3B/P
G20/
G25.3
20/25 G30/G31 30
Hungary II2HS3B/P
G20/
G25.1
25 G30/G31 30
Cyprus, Malta I3B/P -- -- G30/G31 30
Latvia I2H G20 20
Iceland I3P -- -- G31 37
Poland
II2ELwLs-
3B/P
G20/G27/
G2.350 (*)
20/13 G30/G31 37
Russia II2H3B/P G20 20 G30/G31 30