45
12 - FACTORY OPTIONS AND ACCESSORIES
Operating cycle of the burner
■ Burner operation:
When the unit demands heat, the modulation PCB will start the 
operation cycle. It authorises the fl ame monitoring equipment 
to start.
The equipment will immediately start ventilating burner [A] and 
prewashing the combustion chamber for a preset length of time.
After the prewash, the ignition phase starts: the equipment opens 
solenoid EV1 and, in parallel, solenoid EVP which supplies gas 
to the pilot burner [B].
After detecting the pilot fl ame, the equipment opens the main 
gas valve EV2 [C] to supply gas to the main burner.
After a time of dual functioning of the two burners (pilot and 
main), the modulation PCB removes gas from the EVP valve 
and turns off  the pilot burner [D]. 
A single electrode detects the fl ame both for the pilot burner 
and the main burner. 
The ignition program lights the burner to obtain an intermediate 
level heat production capacity, which corresponds to about 30% 
of the maximum capacity. Once the fl ame is stabilised for a few 
seconds at ignition power, the burner begins to modulate its 
output to reach maximum output, if required, in a variable length 
of time programmed into the modulation PCB. 
During operation, the modulation PCB will regulate the power 
output of the burner proportionally to the voltage (0-10 Vdc) in 
the terminals. 
If there are multiple power modules, the 0/10 Vdc signal could 
turn off  one or more modules in cascade. 
■ Turning off  the burner:
When the demand for heating ceases, signalled by a voltage 
lower than the preset limit (0.5 Vdc), the modulation PCB turns 
off  the burner [E]; the fan continues to purge the combustion 
chamber, post-wash, for a preset length of time [F]. 
Opening a contact (see electrical diagram) always causes the 
burner to stop without causing a fault.
■ Safety thermostats:
A safety thermostat with automatic reset and positive safety 
setting is installed on the heater module. The breaking of the 
sensitive element corresponds to a safety intervention.
When the thermostat intervenes, through the fl ame monitoring 
equipment, the burner stops and the flame equipment is 
blocked.
The block of the flame equipment, caused by the safety 
thermostat, is signalled on the LCD display of the CPU PCB on 
the machine with F20. The block is classifi ed as “non-volatile” 
and requires a manual reset.
Near the safety thermostat, there is an NTC1 probe set to the 
value of the ST1 parameter which reduced the burner’s heat 
output independently from the incoming 0/10 Vdc signal when 
is reaches the set point. The probe monitors the ratio of heat 
capacity / cooling air fl ow. It is not advisable to change the 
ST1 value.
On/off signal
Burner fan
EVP - pilot light flame
EV1 - 1st electromagnetic valve gas
EV2 - 2nd electromagnetic valve gas
A BC D E F
Analysis of combustion
Wait until the heater is switched on. Check that the heater is 
running at maximum power by using one of the two methods below:
■ check that Tin input signal is equal to 10 V;
■ from the LCD display, access the REG menu, then use the Hi 
and Lo controls to force operation at maximum or minimum 
output (refer to the paragraph “Control of the gas burner”).
At maximum output, check again that the input pressure in the 
valve corresponds to the value required; adjust if necessary.
Perform the combustion analysis to verify that the level of 
CO
2
 corresponds to the fi gures in the table in Paragraph “Gas 
connection”.
If the measured value is diff erent, turn the adjustment screw on 
the Venturi pipe. Loosening the screw will increase the CO
2
 level, 
screwing it down will decrease the level.
Set the heater to minimum output, and verify that the level of 
CO
2
 corresponds to the fi gures in the tables in paragraph “Gas 
connection”. If the values do not match, screw or loosen the off set 
screw respectively to increase or decrease the CO
2
 level and 
repeat the procedure.