32
NOTE: Some parameters in the menus use the letters MA or
MAT, indicating a mixed air temperature sensor location before
the cooling coil. This unit application has the control sensor lo-
cated after the cooling coil, in the fan section, where it is desig-
nated as (Cooling) Supply Air Temperature or SAT sensor.
Setup and Configuration
Before being placed into service, the W7220 Economizer
module must be set up and configured for the installed
system.
The setup process uses a hierarchical menu structure that is
easy to use. Press the ▲ and ▼ arrow buttons to move for-
ward and backward through the menus and press the button to
select and confirm setup item changes.
Time-Out and Screensaver
When no buttons have been pressed for 10 minutes, the LCD
displays a screen saver, which cycles through the Status
items. Each Status items displays in turn and cycles to the
next item after 5 seconds.
IMPORTANT: Table 8 illustrates the complete hierar-
chy. Your menu parameters may be different depending
on your configuration.
For example if you do not have a DCV (CO
2
) sensor,
then none of the DCV parameters appear and only MIN
POS will display. If you have a CO
2
sensor, the DCV
MIN and DCV MAX will appear.
IMPORTANT: During setup, the economizer module is
live at all times.