35
SYSTEM SETUP
INSTALL 01/01/10 N/A Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG F F or C Sets economizer controller in degrees Fahrenheit or Celsius
EQUIPMENT CONV Conventional or HP CONV = conventional;
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump input from
thermostat or controller.
See Menu Note 4.
AUX2 IN W SD/W or HP(O)/HP(B) In CONV mode:
SD + Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV mode for W.
Shutdown is not available in 2-speed fan mode. See Menu Note 4.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat.
FAN SPEED 2 speed 1 speed/2 speed Sets the economizer controller for operation of 1 speed or 2 speed supply
fan.
NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In.
See Menu Note 4.
FAN CFM 5000cfm 100 to 15000 cfm;
increment by 100
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVAL ENA = AUTO
The value is found on the nameplate label for the specific unit.
AUX1 OUT NONE NONE
ERV
EXH2
SYS
Select OUTPUT for AUX1 O relay
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator
††
• EXH2 = second damper position relay closure for second exhaust fan
• SYS = use output as an alarm signal
OCC INPUT INPUT or ALWAYS OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac), the 24 vac
is input “INPUT” to the OCC terminal. If no occupancy output from the ther-
mostat then change program to “ALWAYS” OR add a jumper from terminal
R to OCC terminal.
FACTORY DEFAULT NO NO or YES Resets all set points to factory defaults when set to YES. LCD
will
briefly
flash YES and change to NO but all parameters will change to the factory
default values.
NOTE: RECHECK AUX2 IN and FANTYPE for required 2-speed values.
ADVANCED
SETUP
MA LO SET 45
°
F 35 to 55
F;
Incremented by 1
0
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and alarm if tem-
perature falls below setup value).
FREEZE POS CLO CLO or MIN FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active (closed or MIN POS).
CO2 ZERO 0ppm 0 to 500 ppm;
Increment by 10
CO
2
ppm level to match CO
2
sensor start level.
CO2 SPAN 2000ppm 1000 to 3000 ppm;
Increment by 10
CO
2
ppm span to match CO
2
sensor.
STG3 DLY 2.0h 0 min, 5 min, 15 min,
then 15 min intervals.
Up to 4 hrs or OFF
COOLING STAGE 3 DELAY
Delay after stage 2 cool has been active. Turns on second
stage of cooling
when economizer is first
stage and mechanical cooling is second
stage.
Allows three stages of cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling
SD DMPR POS CLO CLO or OPN Indicates shutdown signal from space thermostat or unitary controller.
When controller receives 24 Vac input on the SD terminal in conventional
mode, the OA damper will open if programmed for OPN and OA damper
will close if programmed for CLO. All other controls, e.g., fans, etc. will shut
off.
DA LO ALM 45 F (7 C) 35 to 65 F; (2 to 18 C)
Incremented by 5 deg.
Used for alarm for when the DA air temperature is too low. Set lower range
of alarm, below this temperature the alarm will show on the display.
DA HI ALM 80 F (27 C) 70 to 180 F; (21 to 82
C) Incremented by 5
deg.
Used for alarm for when the DA air temperature is too high. Set upper
range of alarm, above this temperature the alarm will show on the display.
DCVCAL ENA MAN MAN (manual) AUTO Turns on the DCV automatic control of the dampers. Resets ventilation
based on the RA, OA, and MA sensor conditions. Requires all 3 RA, OA,
and MA sensors.
ADVANCED
SETUP (CONT)
MAT T CAL 0.0
°
F±2.5
F SUPPLY AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature sen-
sor.
OAS T CAL 0.0
°
F±2.5
F OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature sen-
sor.
OA H CAL 0% RH ±10% RH OUTSIDE AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of calibration humidity sensor.
RA T CAL 0.0
°
F±2.5
F RETURN AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature sen-
sor.
RA H CAL 0% RH ±10% RH RETURN AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of calibration humidity sensor.
DA T CAL 0.0
°
F±2.5
F DISCHARGE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature sen-
sor.
2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1
minute increments
TIME DELAY ON 2nd STAGE ECONOMIZING
When in economizing mode this is the delay for the high speed fan to try to
satisfy the call for second stage cooling before the first stage mechanical
cooling is enab
led.
Table 8 — Menu Structure* (cont)
MENU PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
†
NOTES