EasyManua.ls Logo

Carrier 50TCMD12 - Fan Performance Data

Carrier 50TCMD12
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 5 - Fan Performance
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
1800 785 0.48 0.51 885 0.62 0.66 972 0.76 0.82 1051 0.91 0.98 1121 1.07 1.15
1950 833 0.58 0.62 929 0.74 0.79 1013 0.89 0.95 1089 1.05 1.13 1158 1.21 1.31
2100 881 0.70 0.75 973 0.86 0.92 1054 1.03 1.10 1129 1.20 1.29 1197 1.36 1.48
2250 930 0.84 0.90 1019 1.01 1.08 1097 1.18 1.27 1169 1.34 1.46 1236 1.53 1.66
2400 980 0.99 1.06 1065 1.17 1.26 1141 1.36 1.46 1211 1.53 1.66 1276 1.72 1.87
2550 1030 1.17 1.25 1112 1.36 1.46 1185 1.54 1.67 1253 1.73 1.88 1317 1.93 2.10
2700 1081 1.34 1.46 1159 1.54 1.67 1231 1.75 1.90 1297 1.95 2.12 1358 2.16 2.35
2850 1133 1.56 1.69 1207 1.77
1.92 1276 1.98 2.15
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
1800 1188 1.22 1.33 1249 1.39 1.51 1307 1.57 1.70 1363 1.75 1.90 1373 1.93 2.10
1950 1223 1.37 1.49 1284 1.55 1.68 1342 1.73 1.88 1396 1.92 2.09
2100 1261 1.54 1.67 1320 1.72 1.87 1376 1.92 2.08 1431 2.11 2.29
2250 1298 1.72 1.87 1356 1.92 2.08 1412 2.11 2.29
2400 1337 1.92 2.09 1394 2.13 2.31
2550 1376 2.15 2.33
2700
2850
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
2250 511 0.44 0.48 591 0.61 0.66 660 0.80 0.86 722 1.00 1.07 779 0.82 0.89
2438 540 0.54 0.58 616 0.71 0.77 683 0.91 0.97 743 1.12 1.20 799 0.94 1.02
2625 569 0.64
0.68 642 0.83 0.89 706 1.03 1.11 765 1.24 1.34 819 1.06 1.15
2813 599 0.76 0.81 669 0.96 1.03 731 1.17 1.25 788 1.38 1.49 841 1.19 1.30
3000 630 0.89 0.95 696 1.10 1.18 756 1.31 1.42 811 1.54 1.67 863 1.34 1.46
3188 661 1.03 1.11 724 1.26 1.35 782 1.48 1.60 836 1.72 1.86 886 1.50 1.63
3375 692 1.20 1.29 753 1.42 1.54 808 1.66 1.80 861 1.91 2.08 910 1.67 1.82
3563 723 1.38 1.49 782 1.61 1.75 836 1.87 2.03 887 2.12 2.30
3750 755 1.57 1.70 811 1.82 1.98 864 2.09 2.27
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
2250 832 1.42 1.54 882 1.65 1.79 928 1.90 2.06
2438 851 1.55 1.68 899 1.79 1.94
2625 870
1.69 1.84 918 1.94 2.11
2813 890 1.86 2.02
3000 912 2.04 2.21
3188
3375
3563
3750
Normal Font - Field Installed Drive Package
8. Conversion - Bhp to KWI
1.2
1.4
1.6
1.8
2.0
Legend:
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts
or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
0.2 0.4 0.6 0.8 1.0
0.2 0.4 0.6 0.8 1.0
Unit 50TCM - A07 - 6 Tons - 400V - 50Hz (Continued)
Unit 50TCM - D08 - 7.5 Tons - 400V - 50Hz
Air Flow
Rate (CFM)
Available External Static Pressure (in. wg)
Available External Static Pressure (in. wg)
Available External Static Pressure (in. wg)
Unit 50TCM - A07 - 6 Tons - 400V - 50Hz
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
KWI=
Bhp X 0.746
Motor efficiency
Bold Font - Standard Drive Package + Standard Motor.
Italics Font - Medium Drive Package + Medium Static Motor.
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
RPM - Revolutions Per Minute
KWI - Kilo Watts Input to Motor
BHP - Brake Horsepower Input to Fan
1.2
CFM - Cubic Feet per Minute
in.wg - Inch Water Gage
Notes:
1.4 1.6 1.8 2.0
Available External Static Pressure (in. wg)
Air Flow
Rate (CFM)
Air Flow
Rate (CFM)
Air Flow
Rate (CFM)
Unit 50TCM - D08 - 7.5 Tons - 400V - 50Hz (Continued)