Table 5 - Fan Performance (Continued)
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
3700 621 0.98 1.06 679 1.15 1.25 734 1.33 1.44 786 1.51 1.64 837 1.70 1.84
4063 665 1.21 1.32 717 1.39 1.51 769 1.58 1.72 818 1.78 1.94 866 1.98 2.15
4375 706 1.48 1.61 757 1.68 1.82 805 1.88 2.04 852 2.09 2.27 897 2.31 2.50
4688 749 1.79 1.95 797 2.00 2.17 843 2.21 2.40 887 2.44 2.65 930 2.67 2.89
5000 793 2.14 2.33 838 2.37 2.58 881 2.60 2.82 923 2.83 3.07 965 3.06 3.33
5313 837 2.55 2.77 880 2.78 3.02 921 3.03 3.29 961 3.26 3.54 1000 3.52 3.82
5700 882 3.00 3.25 922 3.24 3.52 961 3.49 3.79
RPM KWI BHP RPM KWI BHP RPM KWI BHP RPM KWI BHP
RPM KWI BHP
3700 885 1.89 2.05 932 2.09 2.27 978 2.30 2.49 1022 2.50 2.72
4063 912 2.19 2.38 957 2.40 2.61 1001 2.61 2.83 1043 2.83 3.07
4375 941 2.52 2.74 984 2.74 2.98 1026 2.97 3.22
4688 972 2.89 3.14 1013 3.12 3.39
5000 1005 3.31 3.59 1044 3.55 3.85
5313
5700
Normal Font - Field Installed Drive Package
8. Conversion - Bhp to KWI
Legend:
1.2
0.6 0.8
Available External Static Pressure (in. wg)
Bold Font - Standard Drive Package + Standard Motor.
Italics Font - Medium Drive Package + Medium Static Motor.
RPM - Revolutions Per Minute
KWI - Kilo Watts Input to Motor
BHP - Brake Horsepower Input to Fan
CFM - Cubic Feet per Minute
in.wg - Inch Water Gage
Notes:
1. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operatin cfm.
2. Static Pressure (i.e Filters) must be added to external static pressure before entering fan performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters and casing loses.
5. Extensive motor and drive testing on these units ensures that the full brake horsepower and watts range of the motor can be utilized with confidence. Using your fan motors up to the watts
or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Bold data shows the range of air flow rate for unit management system, other rpms require field-supplied drive.
7. Use of field-supplied motor may affect wiring size. Contact your Carrier representative for details.
KWI=
Bhp X 0.746
Motor efficiency
Available External Static Pressure (in. wg)
Air Flow
Rate (CFM)
Air Flow
Rate (CFM)
1.4 1.6 1.8 2.0
Unit 50TCM - D14 - 12.5 Tons - 400V - 50Hz
Unit 50TCM - D14 - 12.5 Tons - 400V - 50Hz (Continued)
0.2 0.4 1.0