EasyManua.ls Logo

Carrier 58CTA/CTX - TYPICAL WIRING SCHEMATIC; ELECTRICAL DATA

Carrier 58CTA/CTX
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
TYPICAL WIRING SCHEMATIC
A95236
ELECTRICAL DATA
58CTA/CTX
UNIT SIZE
VOLTS HERTZ
PHASE
OPERATING VOLTAGE RANGE
MAXIMUM
UNIT AMPS
MAXIMUM
WIRE
LENGTH --
FT (M)‡
MAXIMUM
FUSE OR CKT
BKR AMPS†
MINIMUM
WIRE GAGE
Maximum* Minimum*
045-08 115-60-1 127 104 5.3 49 (14.9) 15 14
045-12 115-60-1 127 104 7.1 38 (11.5) 15 14
070-08 115-60-1 127 104 5.2 51 (15.5) 15 14
070-12 115-60-1 127 104 7.3 37 (11.2) 15 14
070-16 115-60-1 127 104 10.1 27 (8.2) 15 14
090-14 115-60-1 127 104 8.2 34 (10.3) 15 14
090-16 115-60-1 127 104 9.9 28 (8.5) 15 14
090-20 115-60-1 127 104 12.9 34 (10.3) 20 12
110-12 115-60-1 127 104 8.2 34 (10.3) 15 14
110-16 115-60-1 127 104 10.1 28 (8.5) 15 14
110-22 115-60-1 127 104 13.7 32 (9.7) 20 12
135-16 115-60-1 127 104 10.2 27 (8.2) 15 14
135-22 115-60-1 127 104 14.5 30 (9.1) 20 12
155-20 115-60-1 127 104 15.0 29 (8.8) 20 12
* Permissible limits of the voltage range at which un it operates satisfactorily.
Time --- delay type is recommended.
Length shown is as measured 1 w ay along wire path between unit and service panel for maximum 2 percent voltage drop.
58CTA/CTX

Related product manuals