15
TYPICAL WIRING SCHEMATIC
A95236
ELECTRICAL DATA
58CTA/CTX
UNIT SIZE
VOLTS HERTZ
PHASE
OPERATING VOLTAGE RANGE
MAXIMUM
UNIT AMPS
MAXIMUM
WIRE
LENGTH --
FT (M)‡
MAXIMUM
FUSE OR CKT
BKR AMPS†
MINIMUM
WIRE GAGE
Maximum* Minimum*
045-08 115-60-1 127 104 5.3 49 (14.9) 15 14
045-12 115-60-1 127 104 7.1 38 (11.5) 15 14
070-08 115-60-1 127 104 5.2 51 (15.5) 15 14
070-12 115-60-1 127 104 7.3 37 (11.2) 15 14
070-16 115-60-1 127 104 10.1 27 (8.2) 15 14
090-14 115-60-1 127 104 8.2 34 (10.3) 15 14
090-16 115-60-1 127 104 9.9 28 (8.5) 15 14
090-20 115-60-1 127 104 12.9 34 (10.3) 20 12
110-12 115-60-1 127 104 8.2 34 (10.3) 15 14
110-16 115-60-1 127 104 10.1 28 (8.5) 15 14
110-22 115-60-1 127 104 13.7 32 (9.7) 20 12
135-16 115-60-1 127 104 10.2 27 (8.2) 15 14
135-22 115-60-1 127 104 14.5 30 (9.1) 20 12
155-20 115-60-1 127 104 15.0 29 (8.8) 20 12
* Permissible limits of the voltage range at which un it operates satisfactorily.
† Time --- delay type is recommended.
‡ Length shown is as measured 1 w ay along wire path between unit and service panel for maximum 2 percent voltage drop.
58CTA/CTX