34
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower door switch opens 115--v power to control. No
component operation can occur. Do not bypass or close
switch with blower door removed.
!
WARNING
See Fig. 33 for field wiring diagram showing typical field 115-- v
wiring. Check all factory and field electrical connections for
tightness.
Field--supplied wiring shall conform with the limitations of 63_F
(33_C) rise.
W/W1
W2
COM
Y/Y2
R
G
A11401
Fig. 33 -- Typical Field Wiring Diagram
Table 9 – Electrical Data
MODULATING
FURNACE SIZE
V O LT S ---
H E R T Z ---
PHASE
OPERATING VOLTAGE
RANGE*
MAX
UNIT
AMPS
UNIT
AMPACITY#
MINIMUM
WIRE
SIZE
AWG
MAXIMUM
WIRE
LENGTH
FT (M)}
MAXIMUM
FUSE OR C KT
BKR
AMPS{
Maximum* Minimum*
060C17---14
1 1 5 --- 6 0 --- 1 127 104 9.0 12.0 14 30 (9.4) 15
060C21---20
1 1 5 --- 6 0 --- 1 127 104 14.1 18.4 12 31 (9.5) 20
080C17---14
1 1 5 --- 6 0 --- 1 127 104 9.0 12.0 14 30 (9.4) 15
080C21---20
1 1 5 --- 6 0 --- 1 127 104 14.1 18.4 12 31 (9.5) 20
100C21---22
1 1 5 --- 6 0 --- 1 127 104 14.1 18.4 12 31 (9.5) 20
120C24---22
1 1 5 --- 6 0 --- 1 127 104 14.1 18.4 12 31 (9.5) 20
* Permissible limits of the voltage range at which the unit operates satisfactorily.
# Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier,
etc.) full l oad amps.
{Time---delay type is recommended.
}Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop.