EasyManua.ls Logo

Carrier 59MN7B - Cooling Mode Operations

Carrier 59MN7B
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
94
The start up and shut down functions and delays described above
apply to the 2-stage minimum/maximum heating mode as well,
except for switching from maximum- to minimum-heat.
1. Switching from Maximum- to Minimum-Heat —Ifthe
thermostat R to W2 circuit opens, and the R to W1 circuit
remains closed, the furnace control CPU will gradually de-
crease the inducer motor speed to the required intermedi-
ate-heat RPM. When the inducer motor IDM reduces pres-
sure sufficiently, the high pressure switch HPS will open
and the gas rate will be changed to intermediate-heat. The
gas valve solenoid GV (pin 5) will remain energized as
long as the low pressure switch LPS remains closed. When
the inducer motor speed gets within 15% of the required
intermediate-heat RPM the furnace control CPU will start a
5 second blower airflow change delay. After the 5 seco nd
blower airflow change delay is completed the blower air-
flow will transition to minimum-heat airflow. At this point
the furnace control CPU will energize the PSR relay to
open the NC contact and slowly decrease the inducer motor
speed to th e req uired min im u m -heat R P M . W h en th e
PSR relay is energized and the NC contact opens the fur-
nace control CPU will reduce the gas rate to minimum-heat
RPM.
Two-Stage Therm ostat and Two-Stage Intermediate/
Maximum Heating
See Fig. 36 and 38 for thermostat connections
NOTE: In this mode the intermediate-heat only switch SW4-2
must be ON to select the intermediate-heat only operation mode in
response to closing the thermostat R to W1 circuit. Closing the
thermostat R to W1-and-W2 circuits always causes
maximum-heat operation, regardless of the setting of the
intermediate-heat only switch.
The wall thermostat ”calls for heat”, closing the R to W1 circuit
for intermediate-heat or closing the R to W1-and-W2 circuits
for maximum-heat. The furnace control performs a self-check, and
verifies the low, medium and high pressure switch contacts LPS,
MPS and HPS are open , then de-energizes the PSR relay to close
the NC contact.
The start up and shut down functions and delays described above
apply to the two-stage intermediate/maximum heating mode as
well, except for switching from maximum- to intermediate-heat.
1. S w itch in g from Ma x im u m - to Interm ed iate-Hea t
If the thermostat R to W2 circuit opens, and the R to W1
circuit remains closed, the furnace control CPU will gradu-
ally decrease the in d u cer moto r sp eed to the requ i red in-
termediate-heat RPM. When the inducer motor IDM re-
duces pressure sufficiently, the high pressure switch HPS
will open and the gas rate will be changed to intermedi-
ate-heat. When the inducer motor speed gets within 15% of
the required intermediate-heat RPM the furnace control
CPU will start a 5 second blower airflow change delay. Af-
ter the 5 second blower airflow change delay is complet-
ed the blower airflow will transition to intermediate-heat
airflow.
Cooling Mode
The thermostat “calls for cooling.”
1. Single-Speed Cooling
See Fig. 36 and 38 for thermostat connections.
The thermostat closes the R to G-and-Y circuits. The R to Y circuit
starts the outdoor unit, and the R to G-and-Y/Y2 circuits start the
furnace blower motor BLWM on cooling airflow. Cooling airflow
isbasedontheA/CselectionshowninFig.65.
The electronic air cleaner terminal EAC-1 is energized with 115
vac when the blower motor BLWM is operating. When the
thermostat is satisfied, the R to G-and-Y circuits are opened. The
outdoor unit will stop, and the furnace blower motor BLWM will
continue operating at cooling airflow for an additional 90 seconds.
Jumper Y/Y2 to DHUM to reduce the cooling o ff-delay to 5
seconds. See Fig. 36.
2. Single-Stage Thermostat and Two-Speed Cooling
(Adaptive Mode)
See Fig. 36 and 38 for thermostat connections.
This furnace can operate a two-speed cooling unit with a
single-stage thermostat because the furnace control CPU includes a
programmed adaptive sequence of controlled op erat ion , which
selects low-cooling or high-cooling operation. This selection is
based upon the stored history of the length of previous cooling
period of the single-stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must be
connected to enable the adaptive cooling mode in response to a
call for cooling. See Fig. 36. When in place the furnace control
CPU can turn on the air conditioning relay ACR to ener gize the
Y/Y2 terminal and switch the outdoor unit to high-cooling.
The furnace control CPU can start up the cooling unit in either
low- or high-cooling. If starting up in low-cooling, the furnace
control CPU determines the low-cooling on-time (from 0 to 20
minutes) which is permitted before switching to high-cooling.
If the power is interrupted, the stored history is erased and the
furnace control CPU will select low-cooling for up to 20 minutes
and then energize the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high-cooling, as
long as the thermostat continues to call for cooling. Subsequent
selection is based on stored history of the thermostat cycle times.
The wall thermostat “calls for cooling”, closing the R to G and- Y
circuits. The R to Y1 circuit starts the outdoor unit on low-cooling
speed, and the R to G-and-Y1 circuits starts the furnace blower
motor BLWM at low-cooling airflow which is the SW3 selection
as shown in Fig. 65.
If the furnace control CPU switches from low-cooling to high
cooling, the furnace control CPU will energize the air conditioning
relay ACR. When the air conditioning relay ACR is energized the
R to Y1-and-Y2 circuits switch the outdoor unit to high-cooling
speed, and the R to G-and-Y1- and-Y/Y2 circuits transition the
furnace blower motor BLWM to high-cooling airflow.
High-cooling airflow is based on the A/C selection shown in Fig.
65.
NOTE: When transitioning from low-cooling to high-cooling the
outdoor unit compressor will shut down for 1 minute while the
furnace blower motor BLWM transitions to run at high-cooling
airflow.
The electronic air cleaner terminal EAC-1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y circuit are
opened. The outdoor unit stops, and the furnace blower BLWM
and electronic air cleaner terminal EAC-1 will remain ener gized
for an additional 90 seconds. Jumper Y1 to DHUM to reduce the
cooling off-delay to 5 seconds. See Fig. 36.
3. Two Stage Thermostat and Two-Speed Cooling
See Fig. 36 and 38 for thermostat connections.
NOTE: The air conditioning relay disable jumper ACRDJ must
be disconnected to allow thermostat control of the outdoor unit
staging. See Fig. 36.
The thermostat closes the R to G-and-Y1 circuits for low cooling
or closes the R to G-and-Y1-and-Y2 circuits for high cooling. The
R to Y1 circuit starts the outdoor unit on low cooling speed, and
the R to G-and-Y1 circuit starts the furnace blower motor BLWM
at low-cooling airflow which is the SW3 selection as shown in
Fig. 65. The R to Y1-and-Y2 circuits start the outdoor unit on
high-cooling speed, and the R to G-and-Y/Y2 circuits start the

Related product manuals