59TP6C: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
A230046
A230047
Fig. 10 – Horizontal Right Trap Configuration
(Appearance may vary)
A230048
A230049
Fig. 11 – Horizontal Left Configuration
(Appearance may vary)
To Relocate the Condensate Trap:
Remove the knockout or plug in the casing for the condensate trap.
Install the grommet in the casing when required for direct-vent
horizontal applications.
Orient the furnace in the desired position.
Allow for 2 in. (51 mm) of clearance underneath the furnace for the
condensate trap and drain line.
Fig. 10 shows the condensate trap and tubing before and after
relocation in the horizontal right position.
Fig. 11 shows the condensate trap and tubing before and after
relocation in the horizontal left position.
Refer to the appropriate figure to begin the trap conversion.
Refer to Condensate Drain section for information how to install the
condensate drain.
A170135
Fig. 12 – Example of Field Drain Attachment
-
-
-
-
-
-
-
-
-
-
-
-