80AW1 - 80AW2
8 User TEMP LIST
Depending on the selection, the following temperatures will
be displayed on the user interface
1 8 1
1. Temperature of the zone:
Zone 1: room temperature
Zone 2: room temperature
Zone 3: Domestic hot water temperature
2. LWT
3. Domestic hot water tempe
4. TWB
5. TW1 (Water temperature in Zone 1)
6. TW2 (Water temperature in Zone 2)
7. Not used
8. Not used
9 User FAULT CODES
Hydronic module, zone kit , user interface and outdoor unit
fault codes and alarms scrolled @ 1 second.
- - -
10 User FAULT HISTORY Stores the recent 4 fault codes and alarms. - - -
INSTALLER PARAMETERS
System setup
100 Inst. SYSTEM TYPE
This parameter is used by the Installer in order to determine
the System type:
1 2 1
Select 1 if there is no kone kit connected, otherwise select 2.
101 Inst. NOT USED
102 Inst. NOT USED
103 Inst. GMC ADDRESS
This parameter is dening if the board is acting as hydronic
module board (master) or zone kit board (slave).
1 2 1
To modify this parameter connect the user interface to the
specic board through J5 connector; user interface wiring
as per connection to W-C-G-Y terminal blocks (see user
interface manual)
1. Master
2. Slave
104 Inst. NUI ADDRESS
Species the user interface connection. If this parameter is
not set properly, user interface does not work.
242 244 242
242. User interface connected on W-C-G-Y, see user interface
manual
243. User interface connected on Rc-Rh-G2-Y2 (see user
interface manual) and placed in zone 1
244. User interface connected on Rc-Rh-G2-Y2 (see user
interface manual) and placed in zone 2
105 Inst. ZONES CTRL
This parameter is dening the Ctrl in zones. Use Day Button
and select the following.
0 4 0
0. Zone 1 CTRL
0. No control
1. User interface (additional user interface, connected on
Rc-Rh-G2-Y2)
2. Sensor
3. Thermostat
4. Unit user interface removed from unit and mounted in
zone; connection on W-C-G-Y
1. Zone 2 CTRL
0. No control
1. User interface (additional user interface, connected
on Rc-Rh-G2-Y2)
2. Sensor
3. Thermostat
4. Unit user interface removed from unit and mounted
in zone; connection on W-C-G-Y
Controller operation
Code
Nr.
Level Variable Name DESCRIPTION
VALUE RANGE
DEFAULT
Min Max