80AWX- 80AWH
Controller operation
Code
Nr.
Level Variable Name DESCRIPTION
VALUE RANGE
DEFAULT
Min Max
106 Inst. INTERFACE CONFIG
Use Days button and do the selection of below
0 1
0. Domestic hot water input - conguration 0
0: contact close: input is active / contact open: input is
not active
1: contact close: input is not active / contact open: input
is active
1. Space heat/cool ON/OFF input - conguration (no impact
on Domestic Hot Water production)
1
0: contact close: unit produces space htg/clg / contact
open: unit does not produce space htg/clg
1: contact close: unit does not produce space htg/clg /
contact open: unit produces space htg/clg
2. Heat / Cool selection input- conguration
1
0: contact close: unit performs space heating / contact
open: unit performs space cooling
1: contact close: unit performs space cooling / contact
open: unit performs space heating
3. Hi energy rate input - conguration
0
0: contact close: high energy rate / contact open:
normal energy rate
1: contact close: normal energy rate / contact open:
high energy rate
4. External HTG/CLG
1
0: Mode (Heat/Cool) is determined by dry contact
1: Mode (Heat/Cool/OFF/Domestic Hot Water) is
determined by user interface (106.2 is ignored)
5. Cool Z1
0
0: Cool in Zone 1 forbidden
1: Cool in Zone 1 permitted
6. Cool Z2
0
0: Cool in Zone 2 forbidden
1: Cool in Zone 2 permitted
7. System ON / OFF input - conguration
0
0: contact close: system OFF / contact open: system
running
1: contact close: system running / contact open:
system OFF
107 Inst.
FLOW SWITCH
CONFIGURATION
Use Days button and do the selection of below
0 1
1
0
0.
0: Open - owing / Short: not owing
1: Short - owing / Open: not owing
1.
0: Do not allow water owing when unit pump is OFF (no
external pump used)
1: Allow water owing when unit pump is OFF (external
pump used)
108 Inst.
MASTER OUTPUT
CONFIGURATION
Use UP/Down buttons for choosing 1 to 10.
1 16 4
1. Fan Coil - Fan coils do not work when Domestic hot water
valve is activated
2. Fan Coil - Fan coils always working
3. Fan coils do not work when Domestic hot water valve is
activated, unless the mode is Cool
4. Dehumidier
5. All alarms
6. Alarms stopping the outdoor unit
7. Alarms stopping the entire system
9. Defrost
10. All alarms + Defrost
11. Alarms stopping the outdoor unit + Defrost
12. Alarms stopping the entire system + Defrost
13. Not used
14. Not used
15. Not used
16. Not used