Table 16 Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
KEYPAD
ENTRY
ITEM
MARQUEE
DISPLAY RANGE
NAVIGATOR
DISPLAY RANGE
ITEM EXPANSION COMMENT
OPT2
(cont)
BAUD 1 - 5
240
0
4800
9600
19,200
38,4
00
CCN BAUD RATE Default: 3
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
LOAD 1 - 2
EQUAL
STAGED
LOADING SEQUENCE
SELECT
Default: 1
1 = Equal
2 = Staged
LLCS 1 - 3 AUTOMATIC
CIR A LEADS
CIR B LEADS
LEAD/LAG CIRCUIT
SELECT
Default: 1 (Size 080-420);
2 (Size 040-070)
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
LCWT
2 - 60
F
(16 - 16
C)
2 - 60
F
(16 - 16
C)
HIGH LCW ALERT
LIMIT
Default: 60
DELY 0 - 15 0 - 15 MINUTES OFF TIME Default: 0
ICE.M ENBL-DSBL ENBL-DSBL ICE MODE ENABLE Default: DSBL
RSET
CRST 0 - 4
NO RESET
4-20 INPUT
OUT AIR TEMP
RETURN FLUID
SPACE TEMP
COOLING RESET
TYPE
0 = No report
2 = 4 to 20 mA input
3 = Return fluid
4 = Space temperature
CRT1
0° - 125 F
(18 - 52 C)
0° - 125 F
(18 - 52 C)
NO COOL RESET
TEMP
Default: 125 F
CRT2
0° - 125 F
(18 - 52 C)
0° - 125 F
(18 - 52 C)
FULL COOL RESET
TEMP
Default: 0° F
DGRC
30 - 30
F
(17 - 17
C)
30 - 30
F
(17 - 17
C)
DEGREES COOL
RESET
Default: 0° F
HRST 0 - 4 0 - 4
HEATING RESET
TYPE
Not Supported
HRT1
0° - 125 F
(18 - 52 C)
0° - 125 F
(18 - 52 C)
NO HEAT RESET
TEMP
Not Supported
HRT2
0° - 125 F
(18 - 52 C)
0° - 125 F
(18 - 52 C)
FULL HEAT RESET
TEMP
Not Supported
DGRH
30 - 30
F
(17 - 17
C)
30 - 30
F
(17 - 17
C)
DEGREES HEAT
RESET
Not Supported
DMDC 0 - 3 0 - 3
DEMAND LIMIT
SELECT
Default: 0
DM20 0 - 100% 0 - 100%
DEMAND LIMIT
AT 2 0 m A
Default: 100%
SHNM 0 - 99 0 - 99
LOADSHED GROUP
NUMBER
Default: 0
SHDL 0 - 60% 0 - 60%
LOADSHED DEMAND
DELTA
Default: 0
SHTM 0 - 120 0 - 120
MAXIMUM LOADSHED
TIME
Default: 60 minutes
DLS1 0 - 100% 0 - 100%
DEMAND LIMIT
SWITCH 1
Default: 80%
DLS2 0 - 100% 0 - 100%
DEMAND LIMIT
SWITCH 2
Default: 50%
LLEN ENBL-DSBL ENBL-DSBL
LEAD/LAG CHILLER
ENABLE
Default: DSBL
MSSL SLVE-MAST SLVE-MAST
MASTER/SLAVE
SELECT
Default: Master
SLVA 0 - 239 0 - 239 SLAVE ADDRESS Default: 0
LLBL ENBL-DSBL ENBL-DSBL
LEAD/LAG BALANCE
SELECT
Default: DSBL
LLBD 40 - 400HRS 40 - 400HRS
LEAD/LAG BALANCE
DELTA
Default: 168 hours
LLDY 0 - 30 MIN 0 - 30 MIN LAG START DELAY Default: 5 minutes
ENTER