EasyManua.ls Logo

Carrier Air Conditioner - Appendix A - Ccn Tables

Carrier Air Conditioner
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
79
APPENDIX A CCN TABLES (cont)
CSM/FSM EQUIPMENT TABLE (Type 621H, Block 2)
WSM EQUIPMENT PART COOL SOURCE MAINTENANCE TABLE
SUPERVISOR MAINTENANCE TABLE
OCCUPANCY MAINTENANCE TABLE
OCCUPANCY SUPERVISORY
LINE DESCRIPTION POINT
1
Chiller Status
0 = Chiller is off
1 = Valid run state in CCN mode
2 = Recycle active
3 = Chiller is in Local Mode
4 = Power Fail Restart in Progress
5 = Shutdown due to fault
6 = Communication Failure
CHILSTAT
2
Lag Status LAGSTAT
3
Percent Total Capacity Running CAP_T
4
Service Runtime HR_MACH
5
unused
6
unused
7
unused
8
Power Fail Auto Restart ASTART
9
Percent Available Capacity On CAP_A
DESCRIPTION STATUS POINT
WSM Active?
Yes WSMSTAT
Chilled water temp
snn.n °F CHWTEMP
Equipment status
On CHLRST
Commanded state
Enable/Disable/None CHLRENA
CHW setpoint reset value
nn.n^F CHWRVAL
Current CHW setpoint
snn.n °F CHWSTPT
DESCRIPTION STATUS POINT
Current Mode (1=Occup.)
0,1 MODE
Current Occup. Period #
0-8 PER-NO
Timed-Override in Effect
Yes/No OVERLAST
Time-Override Duration
0-4 hours OVR_HRS
Current Occupied Time
hh:mm STRTTIME
Current Unoccupied Time
hh:mm ENDTIME
Next Occupied Day
NXTOCDAY
Next Occupied Time
hh:mm NXTOCTIM
Next Unoccupied Day
NXTUNDAY
Next Unoccupied Time
hh:mm NXTUNTIM
Previous Unoccupied Day
NXTUNDAY
Previous Unoccupied Time
hh:mm PRVUNTIM

Table of Contents