INSTALL SPRING ISOLATION
Spring isolation may be purchased as an accessory from Carrier
for field installation. It may also be field supplied and installed.
Spring isolators may be placed directly under machine support
plates or located under machine soleplates. See Fig. 11. Consult
job data for specific arrangement. Low profile spring isolation
assemblies can be field supplied to keep the machine at a conve-
nient working height.
Obtain specific details on spring mounting and machine weight
distribution from job data. Also, check job data for methods to
support and isolate pipes that are attached to spring isolated
machines.
NOTE: The springs are designed to support the weight of the
chiller only. Connected piping must be supported independently of
the chiller.
NOTE: It is recommended that any installation other than the
ground floor should have spring isolation for the chiller and piping
vibration isolation.
NOTE: These isolators are not intended for seismic duty, but are
intended to reduce the vibration and noise levels transmitted
from the chiller to the surrounding environment. For installa-
tions adjacent to areas that are sensitive to noise and/or vibration,
use the services of a qualified consulting engineer or acoustics
expert to determine whether these springs will provide adequate
noise/vibration suppression.
Fig. 11 — 19DV Accessory Spring Isolation (Shown with Accessory Soleplates)
LEVEL
FOUNDATION
ACCESSORY
SPRING
ISOLATOR
RESILIENT SHEER
FLEX PAD, BONDED TO
TOP AND BOTTOM OF
SPRING MOUNT
ENLARGEMENT
OF SPRING
ISOLATOR