EasyManua.ls Logo

Carrier AquaEdge 19DV series - Ground Connector

Carrier AquaEdge 19DV series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
Fig. 25 — 19DV Chiller with VFD
Table 14 — VFD Conductor Usage
LEGEND
1—Disconnect
2—Chilled Water Pump Starter
3—Condenser Water Pump Starter
4—Cooling Tower Fan Starter
(Low Fan, High Fan)
5—Vents
6—HMI (hidden)
7—Unit-Mounted VFD
8—Control Panel
9—Strainers
10 Chilled Water Pump
11 Condenser Water Pump
12 Pressure Gages
Piping
Control Wiring
Power Wiring
NOTES:
1. Wiring and piping shown are for general point-of-connection only and are not
intended to show details for a specific installation. Certified field wiring and
dimensional diagrams are available on request.
2. All wiring must comply with applicable codes.
3. Wiring not shown for optional devices such as:
• Remote Start/Stop
• Remote Alarms
• Optional Safety Device
• 4 to 20 mA Resets
• Optional Remote Sensors
4. IMPORTANT: Carrier suggests that a structural engineer be consulted if trans-
mission of vibrations from mechanical equipment is of concern.
5. Isolation valves are recommended on the evaporator and condenser water pip-
ing to each chiller for service.
6. Operating environment — Chiller should be installed in an indoor environment
where the ambient temperature is 40 to 104°F (4 to 40°C) with a relative
humidity (non-condensing) of 95% or less. To ensure that electrical compo-
nents operate properly, do not locate the chiller in an area exposed to dust, dirt,
corrosive fumes, or excessive heat and humidity.
7. Be sure to pipe
3
/
8
-in. VFD condensate pipe to drain.
4
3
1
1
1
1
2
5
6
7
8
9
11
10
12
VFD MAX INPUT AMPS
STANDARD 100 KAIC LUG CAPACITY (PER PHASE)
NO. OF CONDUCTORS CONDUCTOR RANGE GROUND CONNECTOR
CARRIER 32VSS0850 4 4/0 - 500 kcmil 2/0

Other manuals for Carrier AquaEdge 19DV series

Related product manuals