Step 3 — Install Machine Supports
INSTALL STANDARD ISOLATION
Figure 8 shows the position of support plates and shear flex
pads, which together form the standard machine support system.
INSTALL ACCESSORY ISOLATION (IF REQUIRED)
Uneven floors or other considerations may dictate the use of
accessory soleplates (supplied by Carrier for field installation)
and leveling pads. Refer to Fig. 10.
Chiller support plates must be level within
1
/
4
-in. (6 mm) from
one end to the other.
Level machine by using jacking screws in isolation soleplates.
Use a level at least 24-in. (600 mm) long.
For adequate and long lasting machine support, proper grout
selection and placement is essential. Carrier recommends that
only pre-mixed, epoxy type, non-shrinking grout be used for
machine installation. Follow manufacturers instructions in ap-
plying grout.
1. Check machine location prints for required grout
thickness.
2. Carefully wax jacking screws for easy removal from
grout.
3. Grout must extend above the base of the soleplate and
there must be no voids in grout beneath the plates.
4. Allow grout to set and harden, per manufacturers instruc-
tions, before starting machine.
5. Remove jacking screws from leveling pads after grout has
hardened.
Fig. 10 — Accessory Isolation with Soleplate Package
IMPORTANT: Chiller housekeeping pad, anchor bolts, and
attachment points that are designed by others must be in ac-
cordance with all applicable national and local codes.
TYPICAL ISOLATION
STANDARD ISOLATION
VIEW A-A
NOTES:
1. Optional soleplate package includes 4 soleplates, 16 jacking screws and 16
leveling pads. Isolation package is also required.
2. Jacking screws to be removed after grout has set.
3. Thickness of grout will vary, depending on the amount necessary to level chiller.
Use only pre-mixed non-shrinking grout, Ceilcote
1
748 OR Embeco
2
636 Plus,
0-1½ (38.1 mm) to 0-2¼ (57 mm) thick.
1. Ceilcote is a registered tradmark of Azko Nobel Coatings International.
2. Embeco is a registered trademark of Construction Research and Technology
GMBH Corp.
VIEW B-B
ISOLATION WITH STANDARD PACKAGE ONLY
NOTE: Isolation package includes
4 Shear-Flex isolation pads.