28
Table 9 — Factory Parameters
Table 10 — General VFD Config
Main Menu
Configuration MenuGeneral VFD Config [CFGGEVFD]
Table 11 — 19DV Configuration
Main Menu
Configuration Menu19DV Configuration [Table = CFG_19DV]
DESCRIPTION RANGE UNITS DEFAULT VALUE
Factory Password
0 to 65535 4444 n/a
Chiller Type
19XR6/7=0,
19XR2~E/D/V=1,
19DV=2
0 to 2 0 2
Unit Type
Cool Only=0, Heat Mach=1
0 to 1 0 Per selection
Comp (Single=0, Dual=1)
0 to 1 1 1
Chilled Medium Type
Water/Brine
Water/Brine Water Per selection
Cond Shell Side MAWP
185PSI=0, 300PSI=1
0 to 1 1 n/a
19DV Comp Design Press
44PSI=0, 72PSI=1
0 to 1 0 1
Country Code
0 to 999 86 01
Free Cooling Option
No/Yes No Per selection
VFD Option
No=0,FS VFD=1,Carrier=2,
Rockwell LF2=3, Eaton=4,
Rockwell STD=5
0 to 5 0 2
IOB3 Option (19XR2~E/D/V)
0 to 1 0 n/a
IOB4 Option
No/Yes No Yes
Guide Vane1 Type,
Digital=0, Analog=1
0 to 1 0 1
VFD Feedback Voltage Sel,
0-5V=0, 0-10V=1
0 to 1 0 n/a
Marine Option
0 to 1 0 n/a
Power Request Option
0 to 1 0 n/a
Cont. Power Request
0 to 1 0 n/a
Purge System Option
Dsable/Enable Dsable Enable
Liquid Bypass Option
Dsable/Enable Dsable Per selection
Heat Reclaim Option
No=0, Full=1, Partial=2
0 to 2 0 n/a
DESCRIPTION RANGE UNITS DEFAULT VALUE
VFD Gain 0.10 to 1.50 - 0.75 0.75
VFD Max Speed Per 90.0 to 110.0 % 100 100
VFD Min Speed Per 45.0 to 89.0 % 70 60
VFD Start Speed Per 65.0 to 100.0 % 100 100
VFD Current Limit 0.0 to 99999.0 AMPS 250 Nameplate
VFD Load Current 20mA 10.0 to 5000.0 AMPS 200 n/a
Comp Frequency 100% 45.0 to 62.0 Hz 50 Nameplate
VFD Load Current Input Enable/Dsable - Enable Dsable
DESCRIPTION RANGE UNITS DEFAULT VALUE
Motor Pole Pair 1, 2 - 1 1
IGV2 Travel Limit 30 to 100% % 96 93.6
IGV2 minimum Degree 0 to 20 Degree 2 2
IGV2 Fully Open Degree 10 to 100 Degree 90 88
IGV2 Actuator Max Deg. 90 to 120 Degree 94 94
IGV2 Deg@IGV1 20 Deg 10 to 30 Degree 28.1 28.1
IGV2 Deg@IGV1 30 Deg 10 to 50 Degree 37.2 37.2
IGV2 Deg@IGV1 50 Deg 10 to 80 Degree 71.6 71.6
VFD Rate Speed Hz 10 to 200 Hz 80.5 80.5
Purge Regen Lasting Time 0 to 65535 minutes 120 120
Daily PG Pumpout Limit 20 to 200 minutes 50 50