27
Fig. 26 — 19DV Configuration Tables
Fig. 27 — User Login Screen
INPUT TIME AND DATE — Set day and time and, if appli-
cable, Holidays through MAIN MENU CONFIGURATION
MENU and then select appropriate icon. See the Controls Op-
eration and Troubleshooting guide for details. Because a sched-
ule is integral to the chiller control sequence, the chiller will not
start until the time and date have been set.
NOTE: The date format is YY/MM/DD for English units and
for SI units.
MODIFY CONTROLLER IDENTIFICATION IF NECES-
SARY — The CCN address can be changed from the Config-
uration Menu. Change this address under CONTROL IDEN-
TIFICATION for each chiller if there is more than one chiller
at the jobsite. Write the new address on the PIC5 Touch Screen
module for future reference.
CONFIGURE TABLES Access the related tables
through MAIN MENU CONFIGURATION MENU
(Fig. 26) to modify or view job site parameters shown in
19DV Configuration tables. Tables 9-15 should be verified
or configured during startup/commissioning. Consult chiller
nameplates as indicated.