27
Fig. 26 — 19DV Configuration Tables
Fig. 27 — User Login Screen
INPUT TIME AND DATE — Set day and time and, if appli-
cable, Holidays through MAIN MENU CONFIGURATION
MENU and then select appropriate icon. See the Controls Op-
eration and Troubleshooting guide for details. Because a sched-
ule is integral to the chiller control sequence, the chiller will not
start until the time and date have been set.
NOTE: The date format is YY/MM/DD for English units and
for SI units.
MODIFY CONTROLLER IDENTIFICATION IF NECES-
SARY — The CCN address can be changed from the Config-
uration Menu. Change this address under CONTROL IDEN-
TIFICATION for each chiller if there is more than one chiller
at the jobsite. Write the new address on the PIC5 Touch Screen
module for future reference.
CONFIGURE TABLES — Access the related tables
through MAIN MENU CONFIGURATION MENU
(Fig. 26) to modify or view job site parameters shown in
19DV Configuration tables. Tables 9-15 should be verified
or configured during startup/commissioning. Consult chiller
nameplates as indicated.