Table 20 — 19DV Two-Stage Compressor Frame Size DV4
Heat Exchanger Weights (English)
* Rigging weights are for standard Super B5LSL and Super C5
tubes of standard wall thickness (0.025-in. [0.635 mm] wall) and
do not include refrigerant weight.
† See Model Number Nomenclature on page 5.
NOTES:
1. Evaporator weight includes two-pass Victaulic dished heads.
2. Condenser weight includes the high side float chamber, dis-
charge pipe, and two-pass Victaulic dished heads; does not
include economizer weight.
CODE†
DRY RIGGING WEIGHT (lb)* REFRIGERANT WEIGHT (lb) WATER WEIGHT (lb)
EVAPORATOR
ONLY
CONDENSER
ONLY
EVAPORATOR
ONLY
CONDENSER
ONLY
EVAPORATOR
ONLY
CONDENSER
ONLY
G20 8547 — 700 — 1764 —
G21 8702 — 700 — 1841 —
G22 8864 6633 700 413 1921 1347
G23 9027 6869 700 405 2001 1444
G24 9238 7128 700 402 2105 1549
G25 8547 — 700 — 1764 —
G26 8666 — 700 — 1823 —
G27 8828 6559 700 413 1903 1317
G28 8998 6769 700 405 1987 1403
G29 9182 7017 700 402 2077 1504
G40 9227 — 840 — 1867 —
G41 9410 — 840 — 1956 —
G42 9602 7247 840 468 2049 1490
G43 9794 7525 840 458 2142 1602
G44 10044 7830 840 455 2264 1724
G45 9227 — 840 — 1867 —
G46 9368 — 840 — 1936 —
G47 9560 7160 840 468 2029 1455
G48 9760 7407 840 458 2126 1554
G49 9978 7699 840 455 2231 1672
G2A 8210 — 700 — 1775 —
G2B 8307 — 700 — 1842 —
G2C 8412 6128 700 413 1915 1437
G2D 8514 6327 700 405 1985 1554
G2E 8668 6505 700 397 2092 1660
G2F 8157 — 700 — 1738 —
G2G 8248 — 700 — 1802 —
G2H 8364 6083 700 413 1882 1410
G2J 8490 6256 700 405 1969 1512
G2K 8616 6398 700 397 2055 1596
G4A 8834 — 840 — 1879 —
G4B 8949 — 840 — 1957 —
G4C 9074 6657 840 468 2043 1594
G4D 9194 6892 840 458 2124 1731
G4E 9377 7102 840 448 2249 1854
G4F 8771 — 840 — 1836 —
G4G 8879 — 840 — 1910 —
G4H 9017 6603 840 468 2004 1562
G4J 9166 6808 840 458 2105 1682
G4K 9315 6976 840 448 2206 1780