Table 21 — 19DV Two-Stage Compressor Frame Size DV4
Heat Exchanger Weights (SI)
* Rigging weights are for standard Super B5LSL and Super C5
tubes of standard wall thickness (0.025-in. [0.635 mm] wall) and
do not include refrigerant weight.
See Model Number Nomenclature on page 5.
NOTES:
1. Evaporator weight includes two-pass Victaulic dished heads.
2. Condenser weight includes the high side float chamber, dis-
charge pipe, and two-pass Victaulic dished heads; does not
include economizer weight.
CODE†
DRY RIGGING WEIGHT (kg)* REFRIGERANT WEIGHT (kg) WATER WEIGHT (kg)
EVAPORATOR
ONLY
CONDENSER
ONLY
EVAPORATOR
ONLY
CONDENSER
ONLY
EVAPORATOR
ONLY
CONDENSER
ONLY
G20 3877 318 800
G21 3947 318 835
G22 4021 3009 318 187 871 611
G23 4094 3116 318 184 907 655
G24 4190 3233 318 182 955 702
G25 3877 318 800
G26 3931 318 827
G27 4004 2975 318 187 863 598
G28 4081 3070 318 184 901 636
G29 4165 3183 318 182 942 682
G40 4185 381 847
G41 4268 381 887
G42 4355 3287 381 212 929 676
G43 4443 3413 381 208 972 727
G44 4556 3552 381 206 1027 782
G45 4185 381 847
G46 4249 381 878
G47 4336 3248 381 212 920 660
G48 4427 3360 381 208 964 705
G49 4526 3492 381 206 1012 758
G2A 3724 318 805
G2B 3768 318 835
G2C 3816 2780 318 187 869 652
G2D 3862 2870 318 184 901 705
G2E 3932 2951 318 180 949 753
G2F 3700 318 789
G2G 3741 318 817
G2H 3794 2759 318 187 854 639
G2J 3851 2838 318 184 893 686
G2K 3908 2902 318 180 932 724
G4A 4007 381 852
G4B 4059 381 888
G4C 4116 3020 381 212 927 723
G4D 4170 3126 381 208 964 785
G4E 4254 3222 381 203 1020 841
G4F 3978 381 833
G4G 4028 381 866
G4H 4090 2995 381 212 909 709
G4J 4158 3088 381 208 955 763
G4K 4225 3164 381 203 1001 807