Fig. 65 — Benshaw, Inc. Solid-State Unit Mounted Starter Wiring Schematic (cont)
CHART 1
SYSTEM
VOLTAGE
3 KVA XFMR
FU1-2 AMPS
2 KVA XFMR
FU1-2 AMPS
1 KVA XFMR
FU1-2 AMPS
200 30 20 12
230 30 20 10
346 20 12 7
380 20 12 6
400 15 12 6
415 15 12 6
480 15 10 5
575 128 4
CHART 2
STARTER RLA
RANGE
MX3 CT RATIO
95-135 864:1
136-200 2640:1
201-231 2640:1
232-300 2640:1
301-340 2640:1
341-480 3900:1
481-580 3900:1
581-600 3900:1
601-740 3900:1
741-855 5760:1
856-1250 5760:1
CHART 3
STARTER
RLA RANGE
L1, L2, L3 CONDUCTORS
PER PHASE (LOAD SIDE)
95-205
262 MCM DLO BLK
1 cond per phase
206-259
373 MCM DLO BLK
1 cond per phase
260-298
373 MCM DLO BLK
1 cond per phase
299-398
262 MCM DLO BLK
2 cond per phase
399-501
262 MCM DLO BLK
2 cond per phase
502-597
373 MCM DLO BLK
2 cond per phase
598-687
373 MCM DLO BLK
2 cond per phase
688-791
444 MCM DLO BLK
2 cond per phase
792-854
444 MCM DLO BLK
2 cond per phase
855-979
373 MCM DLO BLK
3 cond per phase
980-1194
444 MCM DLO BLK
3 cond per phase
1195-1390
444 MCM DLO BLK
3 cond per phase