32
Table 3 — ICVC Display Data (cont)
EXAMPLE 5 — HEAT_EX DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are avail-
able for CCN read operation. Those shown with (**) shall support
write operations for the ICVC only.
EXAMPLE 6 — POWER DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are avail-
able for CCN read operation. Those shown with (**) shall support
write operations for ICVC only.
DESCRIPTION STATUS UNITS POINT
**Chilled Water Delta P -6.7-420 PSI CHWPD
Entering Chilled Water 40 245 F ECW
Leaving Chilled Water 40 245 F LCW
Chilled Water Delta T 40 245 ^ F CHW_DT
Chill Water Pulldown/Min -20-20 ^ F CHW_PULL
Calc Evap Sat Temp 40 245 F ERT
**Evaporator Pressure -6.7 420 PSI ERP
Evap Refrig Liquid Temp 40.0 245.0 F EST
Evaporator Approach 0-99 ^ F EVAP_APP
**Condenser Water Delta P -6.7-420 PSI CDWPD
Entering Condenser Water 40 245 F ECDW
Leaving Condenser Water 40 245 F LCDW
Condenser Refrig Temp 40 245 F CRT
**Condenser Pressure -6.7 420 PSI CRP
Condenser Approach 0-99 ^ F COND_APP
Hot Gas Bypass Relay 0/1 OFF/ON HGBYPASS
Surge Prevention Active? 0/1 NO/YES SHG_ACT
Actual Guide Vane Pos 0-100 % GV_POS
Active Delta Tsat 0-200 ^ F CDW_DT
Surge Line Delta Tsat 0-200 ^ F DELTA_TX
Head Pressure Reference 0-100 % HPR
DESCRIPTION STATUS UNITS POINT
Average Line Current 0-999 % AMPS_P
Actual Line Current 0-99999 AMPS AMPS_A
Average Line Voltage 0-999 % VOLT_P
Actual Line Voltage 0-99999 VOLTS VOLT_A
Power Factor 0.0-1.0 POW_FACT
Motor Kilowatts 0-99999 kW KW
**Motor Kilowatt-Hours 0-99999 kWH KWH
Demand Kilowatts 0-99999 kWH DEM_KWH
Line Current Phase 1 0-99999 AMPS AMPS_1
Line Current Phase 2 0-99999 AMPS AMPS_2
Line Current Phase 3 0-99999 AMPS AMPS_3
Line Voltage Phase 1 0-99999 VOLTS VOLT_1
Line Voltage Phase 2 0-99999 VOLTS VOLT_2
Line Voltage Phase 3 0-99999 VOLTS VOLT_3
Ground Fault Phase 1 0-999 AMPS GF_1
Ground Fault Phase 2 0-999 AMPS GF_2
Ground Fault Phase 3 0-999 AMPS GF_3
Frequency 0-99 Hz FREQ
I2T Sum Heat-Phase 1 0-200 % SUM1HEAT
I2T Sum Heat-Phase 2 0-200 % SUM2HEAT
I2T Sum Heat-Phase 3 0-200 % SUM3HEAT