Table 3 — ICVC Display Data (cont)
EXAMPLE 7 — ISM_STAT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are avail-
able for CCN read operation.
EXAMPLE 8 — ICVCPSWD DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight
4. Press .
NOTES:
1. All variables with CAPITAL LETTER point names are available
for CCN read operation. Those shown with (**) shall support
write operations for the ICVC only.
2. To Disable Service Password, force that item to a value of “1”
using Service Tool. Once this has been done, the Service menu
and the ISM (Starter) Config Data screens can be accessed
without a password. This access is cancelled at the time the
user exits the Service menu/screen.
3. If the Remote Reset Option is set to a value of “1” at the ICVC,
alarms may be reset and CCN mode may be reinstated
remotely using Service Tool, Building Supervisor, or Comfort-
WORKS
®
controls.
DESCRIPTION STATUS UNITS POINT
ISM Fault Status 0-255 ISMFLT
Single Cycle Dropout 0-1 NORMAL/ALARM CYCLE_1
Phase Loss 0-1 NORMAL/ALARM PH_LOSS
Overvoltage 0-1 NORMAL/ALARM OV_VOLT
Undervoltage 0-1 NORMAL/ALARM UN_VOLT
Current Imbalance 0-1 NORMAL/ALARM AMP_UNB
Voltage Imbalance 0-1 NORMAL/ALARM VOLT_UNB
Overload Trip 0-1 NORMAL/ALARM OVERLOAD
Locked Rotor Trip 0-1 NORMAL/ALARM LRATRIP
Starter LRA Trip 0-1 NORMAL/ALARM SLRATRIP
Ground Fault 0-1 NORMAL/ALARM GRND_FLT
Phase Reversal 0-1 NORMAL/ALARM PH_REV
Frequency Out of Range 0-1 NORMAL/ALARM FREQFLT
ISM Power on Reset 0-1 NORMAL/ALARM ISM_POR
Phase 1 Fault 0-1 NORMAL/ALARM PHASE_1
Phase 2 Fault 0-1 NORMAL/ALARM PHASE_2
Phase 3 Fault 0-1 NORMAL/ALARM PHASE_3
1CR Start Complete 0-1 FALSE/TRUE START_OK
1M Start/Run Fault 0-1 NORMAL/ALARM 1M_FLT
2M Start/Run Fault 0-1 NORMAL/ALARM 2M_FLT
Pressure Trip Contact 0-1 NORMAL/ALARM PRS_TRIP
Starter Fault 0-1 NORMAL/ALARM STRT_FLT
Motor Amps Not Sensed 0-1 NORMAL/ALARM NO_AMPS
Starter Acceleration Fault 0-1 NORMAL/ALARM ACCELFLT
High Motor Amps 0-1 NORMAL/ALARM HIGHAMPS
1CR Stop Complete 0-1 FALSE/TRUE STOP_OK
1M/2M Stop Fault 0-1 NORMAL/ALARM 1M2MSTOP
Motor Amps When Stopped 0-1 NORMAL/ALARM AMPSTOP
Hardware Failure 0-1 NORMAL/ALARM HARDWARE
MENU
STATUS
ISM_STAT
SELECT
DESCRIPTION STATUS UNITS POINT
Disable Service Password 0-1 DSABLE/ENABLE PSWD_DIS
**Remote Reset Option (See Note 3) 0-1 DSABLE/ENABLE RESETOPT
Reset Alarm? 0-1 NO/YES REMRESET
CCN Mode? 1 YES REM_CCN