EasyManua.ls Logo

Carrier Aquaforce 30XA Series - Page 119

Carrier Aquaforce 30XA Series
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
119
FLOW SWITCH
Fig. 40 — Flow Switch
a30-5323
BAD
BAD
GOOD
GOOD
Fig. 41 — Tank Baffling
a30-3185
PT
PT
T1
PP
PP
D
D
PT
PT
CHILLED
WATER OUT
HEATER
E
PT
Air Separator with Vent*
Strainer/Suction Guide
Pump
Combination Valve
Isolation Valve*
Pressure Reducing
Fill Valve*
Flexible Connections*
Pressure Relief*
CHILLED
WATER IN
HYDRONIC PUMP PACKAGE
INSIDE
UNIT
OUTSIDE
UNIT
20 Mesh Stainer**
T2
FS
V
D
HEATER
V
D
HEATER
LEGEND
*Field-supplied and installed.
†Factory-installed option.
**Required within 10 ft (3 m) of cooler in addition
to suction strainer for open loop systems.
D Drain,
3
/
4
-in. NPT
D Drain,
1
/
4
-in. NPT
E Expansion Tank Connection,
3
/
4
-in. NPT
FS Flow Switch
PP Pipe Plug,
1
/
4
-in. NPT
PT Pressure/Temperature Tap
T1 Leaving Water Thermistor
T2 Entering Water Thermistor
V Vent,
1
/
4
-in. NPT
Indicates items provided with the
optional hydro
nic pump package.
a30-5296
Fig. 42 — Typical Piping Diagram on 30XA Units with Hydronic Package — Single Pump (Flooded Cooler)