Table 3 — 30XA Minimum and Maximum Cooler Flow Rates (cont)
*For applications requiring cooler leaving water temperature operation at less than 40
F (4.4 C), the units require the use of antifreeze and application may require the brine
option. Contact your local Carrier representative for more information.
†For applications requiring cooler entering water temperature operation at less than 45
F (7.2 C), contact your local Carrier representative for unit selection using the Carrier
electronic catalog.
** For minimum cooler flow rate with brine a
pplications, refer to E-CAT software perfor-
mance.
NOTES:
1. The 30XA units will start and pull down with loop temperatures up to 95 F (35 C).
2. Nominal flow rates required at AHRI (Air Conditioning, Heating, and Refrigeration In-
stitute) conditions 44 F (7 C) leaving fluid temperature, 54 F (12 C) entering water
temperature, 95 F (35 C) ambient. Fouling factor 0.00010 ft
2
-hr-F/Btu (0.000018 m
2
-
K/kW).
3. To obtain proper temperature control, cooler loop fluid volume must be at least 3 gal/
ton (3.23 L/kW) of chiller nominal capacity for air conditioning and at least 6 gal/ton
(6.5 L/kW) for process applications or systems that must operate in low ambient tem-
peratures (below 32 F [0° C]).
ITEM MINIMUM MAXIMUM
Cooler Leaving Water Temperature* 40 F (4.4 C) 60 F (15 C)
Cooler Entering Water Temperature† 45 F (7.2 C) 70 F (21.1 C)
30XA
UNIT SIZE
Nominal Flow Rate
Cooler
Nu
mber of
Passes
Minimum Flow Rate** Maximum Flow Rate
(gpm) (L/s) (gpm) (L/s) (gpm) (L/s)
401 948 59.9
Standard, Flooded 2 474 29.9 1896 119.6
Plus One Pass, Flooded — — — — —
Minus One Pass, Flooded 1 800 50.5 3792 239.3
450 1019.3 64.3
Standard, Flooded 1 501 31.6 2004 126.4
Plus One Pass, Flooded — — — — —
Minus One Pass, Flooded — — — — —
451 1047 66.1
Standard, Flooded 2 523.5 33.0 2094 132.1
Plus One Pass, Flooded — — — — —
Minus One Pass, Flooded 1 800 50.5 40
00 252.4
476 1104 69.7
Standard, Flooded 2 552 34.8 2208 139.3
Plus One Pass, Flooded — — — — —
Minus One Pass, Flooded 1 950 59.9 4000 252.4
500 1092.8 68.9
Standard, Flooded 1 501 31.6 2004 126.4
Plus One Pass, Flooded — — — — —
Minus One Pass, Flooded — — — — —
501 1184 74.7
Standard, Flooded 2 592 37.3 2368 149.4
Plus One Pass, Flooded — — — — —
Minus One Pass, Flooded 1 950 59.9 4000 252.4