Table 5 — 30XA080-500 Electrical Data, Single Point (Standard Condenser Fan Motors) (cont)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the control
power supply disconnect is on, even if any safety device is open.
3. For MCA
that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a
. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is 1/
0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
250 kcmil to 500 kcm
il.
5. Data provided circuit 1/circuit 2 where there are two circuits.
6. Standard condenser fan motors are not used with sizes 30XA-401, 451, 476, and 501.
These sizes use high ambient temperature condenser fans.
UNIT
30XA
UNIT VOLTAGE
NUMBER
OF
COND
FANS
NO HYDRONIC PACKAGE 5 HP PUMP, 3450 RPM 7.5 HP PUMP, 3450 RPM CONTROL CIRCUIT
V-Hz
(3 Ph)
Supplied
MCA MOCP
ICF Rec
Fuse
Size
MCA MOCP
ICF Rec
Fuse
Size
MCA MOCP
ICF Rec
Fuse
Size
Voltage
1 PH,
60 Hz
MCA
and
MOCP
Min Max WD XL WD XL WD XL
450
460-60 414 506 22 880.0 1000 1080.0 2302.0 1000 115 60
575-60 518 633 22 674.6 800 847.8 1825.8 800 115 60
380-60 342 418 22 1022.7 1200 1284.8 2763.8 1200 115 60
500
460-60 414 506 22 931.3 1200 1131.3 2353.3 1200 115 60
575-60 518 633 22 714.1 800 887.3 1865.3 800 115 60
380-60 342 418 22 1082.4 1200 1344.5 2823.5 1200 115 60
ICF Instantaneous Current Flow
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
WD Wye-Delta
XL Across-the-Line